Install & maintenance guide for the Ultraflex/FFI CRM Control Panel and Weather Detection System for motorized window/skylight actuators.
Complete install & maintenance guide for the Ultraflex Control Systems (UCS/FFI) CRM Control Panel and Weather Detection System — for motorized window and skylight actuators. Covers the CRM3 (DC actuators, part# 40821J) and CRM4 (AC actuators, part# 40822K).
| Spec | CRM3 (DC, part# 40821J) | CRM4 (AC, part# 40822K) |
|---|---|---|
| Supply Voltage | 115 Vac ±10%, 60Hz | 115 Vac ±10%, 60Hz |
| Total output (all 4 groups)* | 4 amps @ 24 Vdc | 7 amps @ 115 Vac |
| Power Cable | 2 wires (polarity inversion) | 4 wires (Open, Close, Common, Ground) |
| Safety Marks | CE rated, not UL-Recognized | CE rated, not UL-Recognized |
| Operating environment | 14° to 140°F (-10° to 60°C) | 14° to 140°F (-10° to 60°C) |
| Max. Relative Humidity | 60% | 60% |
| Case Dimensions | 7-13/16" x 5-11/16" x 3-1/8" | 7-13/16" x 5-11/16" x 3-1/8" |
*FFI recommends not exceeding 80% of maximum amp capacity for control panels.
The CRM3 (24 Vdc Control Panel, part# 40821J) delivers power directly to low-voltage actuators, or serves as a switch for multiple RB24 Relay Boxes. It independently controls 1–4 actuator groups via output terminals M1-M4, subject to a max current draw of 4 amps across any combination of the 4 terminals. Input power is 115 Vac, 60Hz; a back-up power source can be connected at the JP4 terminal inside the case.
The CRM4 (115 Vac Control Panel, part# 40822K) delivers power directly to line-voltage actuators. It independently controls 1–4 actuator groups via M1-M4, subject to a max current draw of 7 amps across any combination. Input power is 115 Vac, 60Hz; a back-up power source can also be connected at JP4.
The Control Panel's four actuator groups start up sequentially to eliminate excess current draw risk.
The Control Panel receives commands from optional accessories, which can trigger an "alarm state" causing actuators to close the windows. Alarm State 1 persists for a minimum of 8 minutes, during which windows cannot be opened via Keypad, Momentary Switch, or External Control System (unless rain/wind sensors are disabled).
| Control Accessory | Alarm State Seniority | Min. Duration | Enable/Disable Switch |
|---|---|---|---|
| Rain sensor | 1 | 8 minutes | External switch on Control Panel |
| Wind detector | 1 | 8 minutes | External switch on Control Panel |
| Thermostat | 2 | 3 minutes | External switch on Thermostat |
| Push-button Keypad | 3 | 3 minutes | N/A |
| Infra-red Remote Control | 3 | 3 minutes | N/A |
| Momentary contact switch / external control | 3 | 3 minutes | N/A |
Check that the Control Panel's electrical fuses are in place (see Fuse table below).
A single-pole double-throw (SPDT) momentary contact switch or external control system connects at terminal JP7, delivering OPEN/CLOSE commands as brief impulse signals (0.5–2 sec). The Control Panel acts on all four actuator groups, as if commanded from a Keypad with all 4 LEDs on. Both Keypad and Momentary Switch can be connected simultaneously. Wall switch spec: 15 amps max draw per switch (DC motors with CRM or relay box); dimensions 4" x 1-1/4" x 1-1/2".
Connects at terminals JP5/JP6; multiple keypads can be wired in parallel. Dimensions: 3" x 3" x 1-1/2". Allows independent control of 1–4 actuator groups via serial communication.
Use SELECT to light 1, 2, 3, 4, or all 4 LEDs (one per actuator group), then press OPEN or CLOSE to activate; press the opposite button once to stop the motor. The Control Panel delivers power for a 3-minute interval, then cuts off as a safety precaution. The Keypad has an 8-channel IR detector for the Remote Control — channel 0 (factory default) accepts all frequencies; channels 1-7 restrict to that channel only.
Uses serial protocol and line-of-sight IR signals — must be pointed at the Keypad, not the actuator. Effective range ~30 feet. Requires two 1.5V AAA alkaline batteries (not included). Dimensions: 4" x 1-13/16" x 1". Has an 8-channel IR transmitter matching the Keypad's channel setting (0 = factory default).
Connects at terminal JP9, sending a variable signal per wind intensity. An 8-position selector inside the Control Panel sets the closing threshold ("0" disables; 1-7 correspond to the Beaufort scale). One sensor can serve up to six CRM Control Panels. Disable via the external switch on the Control Panel case. Dimensions: 4-1/2" x 4" x 4".
| Selector | Beaufort | Knots | Mi/Hr | Feet/sec | Description |
|---|---|---|---|---|---|
| 0 | 0 | 0 | 0 | 0 | calm |
| 1 | 1 | 1-3 | 1-3 | <7 | light air |
| 2 | 2 | 4-6 | 4-7 | 7-10 | light breeze |
| 3 (factory) | 3 | 7-10 | 8-12 | 11-16 | gentle breeze |
| 4 | 4 | 11-16 | 13-18 | 17-23 | moderate breeze |
| 5 | 5 | 17-21 | 19-24 | 24-33 | brisk breeze |
| 6 | 6 | 22-27 | 25-31 | 34-43 | strong breeze |
| 7 | 7 | 28-33 | 32-38 | 44-53 | near gale |
Single threshold setting — windows open when ambient temperature rises above threshold, close when below. Rain and wind sensors take priority over the thermostat. Disable via the external ON/OFF switch on the thermostat case. One thermostat can connect to up to six CRM Control Panels. Dimensions: 3" x 3-1/4" x 1-1/2".
Connects at terminal JP8. One sensor can connect to up to six CRM Control Panels. Mount outdoors with the copper-colored grid exposed to the sky. Dimensions: 1-1/2" x 2" x 2". Has a heating element to prevent ice formation.
Actuator groups connect at output terminals M1, M2, M3, M4. CRM3 (24 Vdc, part# 40821J) delivers power directly to DC low-voltage actuators or switches multiple RB24 Relay Boxes, controlling 1–4 groups at up to 4 amps combined. CRM4 (115 Vac, part# 40822K) delivers power directly to AC line-voltage actuators, controlling 1–4 groups at up to 7 amps combined. Both require 115 Vac, 60Hz input; a back-up power source connects at JP4 in either case.
| Fuse | Controls | CRM3 | CRM4 | Part # |
|---|---|---|---|---|
| A | Transformer | 5x20 5A (fast) | 5x20 5A (fast) | 58812L |
| B | Input & Output Line Voltage | 5x20 1A (time delayed) | 5x20 1A (time delayed) | 82983N |
| C | Input & Output Line Voltage | None | 5x20 6.3A (time delayed) | 82982M |
| D | Input & Output Line Voltage | None | 5x20 6.3A (time delayed) | 82982M |
A passive device controlling low-voltage actuators via output terminals Motor1 and Motor2, up to 10 amps per terminal (20 amps per Relay Box). It handles polarity reversal for Motor1/Motor2. An SPDT momentary contact switch or external control system connects at terminal CN6, delivering OPEN/CLOSE impulse signals (0.5–2 sec) that operate all actuators on the Relay Box.
Manufacturer's Limited Warranty: Ultraflex Control Systems S.r.l. (UCS) products are guaranteed against defects in material and workmanship for two years from the date of manufacture. Defective products returned freight-prepaid within the warranty period will be repaired or replaced free of charge at UCS's option. Does not cover direct/indirect damages from improper installation or misuse. UCS motors must be used with UCS-approved accessories; substitutions must meet UCS specifications. Functional Fenestration Inc. (FFI) honors this warranty for two years from the date of sale on FFI's invoice.
FFI Terms: FFI's liability for any defective product is limited to replacement or credit at original cost — no incidental or consequential damages. Claims and returns must follow FFI Terms and Conditions.
Disposal: Dispose of responsibly — the aluminum case and other reusable elements should be recycled.