    Technical specification sheet for the Sensaphone 1400 and 1800 remote monitoring systems, covering input zones, relay output, power supply/battery backup, phone interface, and environmental/physical specs.

    Full text manual (for reference)

    Technical specifications for the Sensaphone 1400 & 1800 remote monitoring systems.

    Input Zones

    • Number of Zones: 1400 model — 4 zones; 1800 model — 8 zones
    • Zone Connector: terminal block
    • Zone Types: N.O./N.C. contact, 2.8K thermistor (-109° to 115°F, -85° to 57°C), 10K thermistor (-87° to 168°F, -66° to 76°C), 4-20mA (-10,000.0 to 10,000.0)
    • Zone Characteristics: 10KΩ to 5V (temperature/contact) or 237Ω to ground (4-20mA)
    • A/D Converter Resolution: 10 bits ±2 LSB

    Relay Output

    Rated for 2A 120VAC / 2A 24VDC maximum. Programmable for manual or automatic switching.

    LED Indicators

    Zone Alarms (4 or 8), Sound, Power, Battery OK, Phone in Use, Output On, System On.

    Microphone

    • Internal: for recording custom voice messages
    • External (optional): for listening in to on-site sounds and high sound level alarms (terminal block mic connector)

    Power Supply

    • Power Supply: 120VAC 50/60Hz — 15V (1800) / 12V (1400) wall plug-in transformer w/6' cord
    • Power Consumption: 5 Watts
    • Power Protection: Metal Oxide Varistor
    • 1800 Battery Backup: 12V 2.2 AH sealed gel cell, up to 12 hours of battery backup
    • 1400 Battery Backup: 6V 1.3 AH sealed gel cell, up to 24 hours of battery backup

    Phone Interface

    • Line RJ11 Terminal: for connection to a two-wire analog telephone line
    • Extension RJ11 Terminal w/ Line Seizure: for connecting other devices on the same telephone line; devices connected to this jack are disconnected in the event the unit must dial out for an alarm
    • Phone Line Protection: Metal Oxide Varistor & self-resetting fuse

    Environmental

    • Operating Temperature: 32° to 122°F | 0° to 50°C
    • Operating Humidity: 0–90% RH non-condensing
    • Storage Temperature: 32° to 140°F | 0° to 60°C

    Physical

    Model Dimensions Weight
    1400 12.1 x 7.3 x 4.5" | 307 x 185 x 114mm 5 lbs. | 2.2kg
    1800 12.1"h x 8.0"w x 5.50" | 307 x 203 x 140mm 8 lbs. | 3.6kg

    Enclosure: NEMA-4 rated plastic housing.

    Manufacturer

    Sensaphone — 901 Tryens Road, Aston, PA 19014. PH: 877-373-2700, F: 610-558-0222. www.sensaphone.com