  • SDC EH Series — Magnetic Door Holder & Releasing Device Datasheet

    September 08, 2026 3 min read

    Datasheet for the SDC EH Series Magnetic Door Holder & Releasing Device, covering the EH10/EH20/EH30/EH40/EH42 mounting configurations.

    Full text manual (for reference)

    Datasheet for the SDC EH Series Magnetic Door Holder & Releasing Device — a fail-secure electromagnetic door holder designed to hold fire/smoke barrier doors open and release them on command or power loss.

    Overview

    SDC EH Series Magnetic Door Holders are designed to hold doors open and release the door via remote switch or fire/life-safety command center activation. Their primary application is holding and releasing fire-rated doors that must act as a barrier for fire and smoke in an emergency, or offering the convenience of remote door closure. Doors are released and closed automatically upon power loss or fire/life-safety system activation.

    Key Features

    • Field-selectable high holding force: 75 or 110 lb
    • For self-closing fire & smoke barrier doors
    • Choice of 25, 30, 35, or 40 lb standard holding force, determined by the unit's specified voltage
    • Very low power consumption — 15mA, 20mA, or 40mA depending on model
    • Choice of 3 dual AC/DC voltage inputs: 12/24V, 24/120V, or 24/220V
    • Screw terminal block input connections — no wire nuts or pigtails needed
    • Innovative self-aligning catch plate and adjustable magnet centerline; ball-pivot assembly enables full plate contact and holding force
    • Optional adjustable rod compensates for misalignment up to 4 inches
    • Slotted mounting holes for centerline adjustment

    Models

    Model Description
    EH10 Flush Mount
    EH20 Semi-Flush Mount
    EH30 Surface Mount
    EH40 Floor Mount, Single
    EH42 Floor Mount, Double

    Specifications

    Spec Value
    Materials Zinc alloy
    Voltage Standard dual voltage AC or DC inputs: 12 & 24V, 24 & 120V, or 24 & 220V models
    Holding force Typical 25–40 lb; can be increased to 75 lb or 110 lb on special applications
    Mount Single or double coil floor, surface, flush, or recessed mount
    Total projection Flush: 2-11/32"; Semi-flush: 3-1/16"; Surface: 4-5/8"; Floor (single): 5"; Floor (double): 9-5/8"
    Fasteners Hardware package, mounting bracket. Optional aluminum extension and misalignment rods available. Drill fixture available.
    Notes Replacement catch plate and catch plate assembly available; adhesive template included

    Performance Data

    Model Voltage DC/mA AC/mA Terminals Holding force
    1224 12V 40 38 C&L 30 lb (13.6 kg)
    1224 24V 40 36 C&H 30 lb (13.6 kg)
    24120 24V 20 19 C&L 40 lb (18.1 kg)
    24120 120V 20 C&H 35 lb (15.8 kg)
    24220 24V 20 19 C&L 40 lb (18.1 kg)
    24220 220V 15 C&H 25 lb (11.3 kg)

    High holding force / special applications: model 1224 at 24V (85/81 mA) via C&L terminals delivers 75 lb (34.0 kg); model 24120 at 120V (100 mA) via C&L delivers 110 lb (49.8 kg). To achieve these values, apply the high listed voltage to the low-voltage terminals (C & L) — applicable only to models 1224 and 24120.

    Ordering

    Sample SKU: EH30 1224 A. Order by specifying: (1) Model — EH10/EH20/EH30/EH40/EH42; (2) Voltage — 1224 (12/24VAC/DC), 24120 (24VAC/DC/120VAC), or 24220 (24VAC/DC/220VAC); (3) Finish — A (Chrome Powder Coat) or B (Black Powder Coat).

    Accessories

    • Extension Rods (EHR02, EHR1, EHR15, EHR2, EHR3, EHR4, EHR5): provide increased reach for the armature catch plate to ensure proper alignment. Flush mount: subtract 3" from measured distance for minimum rod length. Recessed mount: subtract 2-3/8". Surface mount: subtract 4-5/8".
    • Adjustable Extension Rods (EHRA15, EHRA4): for misaligned catch plate/door holder applications.
    • EHBB Surface Back Box (2-25/32" x 4-7/8" x 1-1/2"), supplied with EH30, EH40, EH42; specify finish A or B.
    • EHDF Drilling Fixture — attaches to the door for quick, accurate hole location.
    • EHCP Catch Plate — replacement for the catch plate assembly.
    • EHW Extension Wrenches — used to tighten extension rods to the catch plate assembly.
    • EHSB Catch Plate Assembly — swivel design allows the catch disc to move in all directions to assist with slight misalignment.

    About SDC