August 31, 2026 8 min read
Installation instructions for the NAPCO StarLink SLE Series Alarm Communicators (including SLE-CDMA and SLE-CDMA-8D models).
Installation instructions for the NAPCO StarLink™ SLE Series Alarm Communicators (including SLE-CDMA and SLE-CDMA-8D models) — fully supervised, wireless digital two-way subscriber units that report alarm signals over a cellular network as a backup or primary communicator for 12VDC alarm control panels.
StarLink radio communicators use proprietary data-capture technology to capture alarm reports from the control panel and transmit them to the SLE Control Center, which forwards signals to any central station via standard receiver formats (4/2 and Contact ID). The SLE Control Center also generates a Supervisory signal if the expected supervisory test signal isn't received during a scheduled period.
Additional components: SLE-DLEXT (download extender, 10-100 ft), SLE-DLCBL (6 ft download cable), SLE-SMTCHG (smart charge module/optional charger), SLE-ANTEXT (extended antenna with 15 ft cable).
17 terminals located at the bottom of the StarLink radio PC board:
| Terminal | Function |
|---|---|
| TB1 | PWR (+12V) |
| TB2 | PWR GND (–) |
| TB3 | PGM1 (–), open collector, normally on (active low); triggers open collector/high on trouble. Reconfigurable via Management Center (napconoc.com). |
| TB4 | PGM2 (–), defaults to "Fail to Communicate", active low on failed report. |
| TB5 | PGM3 (–), defaults to "Telephone Line Cut", active low when 24V phone line voltage is too low. |
| TB6 | IN 1 (B/F) — active high input wired to control panel bell output. Steady high = burglary alarm; pulsing temporal high = fire alarm; "CO Alarm" pattern = CO alarm. Requires central station telephone number/reporting format configured. High = armed, low = disarmed for arm/disarm status use (use IN2/IN3 instead if using Napco Armed Lugs E4/E15). |
| TB7 | IN 2 (see TB9) |
| TB8 | GND — common ground terminal |
| TB9 | IN 3 — IN2/IN3 are active-low by default; can be reconfigured via jumpers 4/5 as supervised EOLR inputs triggered by N/O or N/C relay contacts (wire GND/TB8 to relay common). Low = armed, high = disarmed for status use. |
| TB10 | TIP (see TB11) |
| TB11 | RING — TIP/RING: for backup reporting, route street/cable-modem Tip and Ring wires here. Monitored for voltage; if it falls below 1.5V, a Telco Line Fault is detected and the radio switches over to supply its own Telco voltage to the panel. |
| TB12 | PANEL RING (see wiring diagrams) |
| TB13 | PANEL TIP (see wiring diagrams) |
| TB14 | RTS (R) (see TB17) |
| TB15 | PANEL TX (B) (see TB17) |
| TB16 | PANEL RX (G) (see TB17) |
| TB17 | CTS (Y) — wired to the SLE-DLEXT download extender for remote downloading to compatible Gemini/Freedom panels. |
Every 30 seconds the radio checks cell tower signal and blinks 1-8 times. Acceptable power level is ≥ -91dBm (minimum 4 blinks at mounting location).
| LED Blinks | 8 | 7 | 6 | 5 | 4 | 3 | 2 | 1 |
|---|---|---|---|---|---|---|---|---|
| Power (dBm) | -55 | -65 | -75 | -85 | -91 | -95 | -99 | -105 |
Blinks momentarily every 10 seconds in standby. During alarm processing, blinks variably through dialing/handshaking/data transmission phases.
| Blinks | Meaning |
|---|---|
| 1 | Low Aux Power input voltage |
| 2 | Battery trouble |
| 3 | Alarm report failed to communicate |
| 4 | RF trouble (antenna connection or cellular registration) |
| 5 | Network trouble (signal unable to reach SLE Control Center) |
| 6 | Unit disabled (reporting/downloading not allowed) |
| 7 | Unit shut down, no functionality — requires full power cycle to restore |
| 8 | Telco Line Cut |
Red Diagnostic LED (D7): One blink = weak/no network signal (green LED off). Any other blink pattern — contact technical support.
| Jumper # | ON | OFF |
|---|---|---|
| 1 | Do not use unless instructed | Normal operation |
| 2 | 4/2 with Checksum Pulse Format | 4/2 Pulse Format |
| 3 | Backup Mode | Primary Mode |
| 4 | 10K EOLR required | No EOLR for Zone 3 |
| 5 | 10K EOLR required | No EOLR for Zone 2 |
For primary reporting (no telephone lines present, connected directly to panel Telco terminals): do NOT install jumper 3. For backup reporting (existing phone lines present): install jumper 3 — the radio automatically switches to the network when it senses telephone line trouble.
| NOC Telephone # | Max Retry Attempts | Comments |
|---|---|---|
| Primary | 3 | Primary central station number used |
| Backup | 6 | Backup central station number used |
WARNING (FCC RF Exposure): This unit must be installed with a minimum separation of 60cm (24") between the antenna and nearby persons. Use ONLY the supplied antenna (or the SLE-ANTEXT extended antenna) to comply.
| Event | Area | Contact ID | Zone # | Pulse 4/2 |
|---|---|---|---|---|
| IN 1 Fire | 0 | E110 | 990 | 1A |
| IN 1 Burg | 0 | E130 | 991 | 31 |
| IN 2 Panic | 0 | E120 | 992 | 22 |
| IN 3 Trouble | 0 | E300 | 993 | F3 |
| Low Battery/Voltage | 0 | E302 | 994 | F4 |
| Tamper Trouble | 0 | E341 | 995 | F5 |
| Line Cut | 0 | E352 | 996 | F6 |
| Reboot | 0 | E625 | 997 | F7 |
| IN 1 CO (Carbon Monoxide) | 0 | E162 | 998 | 18 |
These event codes and zone numbers can be changed via the Management Center screen at www.napconoc.com. Contact ID is always available in response to a Contact ID handshake.
Use PCD-Windows Quickloader software (Digital Communications screen, Central Station Receivers tab) to program the central station receiver reporting format. If using "4/2 with checksum" format, install jumper #2 in block X5. Always confirm with the central station which receiver format each phone number expects. Supported formats: Contact ID, Ademco Slow, Radionics Fast/Slow, Silent Knight Fast, Universal High Speed. Caution: Always confirm an area code is programmed into the control panel.
Three methods to have the Red Trouble LED (D5) troubles annunciated:
Any signal sent to the central station resets the supervisory time counter to that day. Example: if the scheduled supervisory check-in is March 25 at 3AM, but an alarm signal was sent on March 15 at 3PM, the next check-in moves to April 15 (not April 25) if no other signals are sent.
For single-conductor terminal blocks, don't daisy-chain multiple conductors directly into one terminal — use a pigtail with a wire nut/crimp connector, or connect a single incoming wire. For barrier-type terminal blocks with two conductors, use separate incoming/outgoing conductor terminals rather than doubling up on one side. For more than two conductors or mixed wire gauges, always use the pigtail method with insulated wire and an appropriately sized wire nut/crimp connector.
The full PDF includes detailed primary and backup wiring diagrams for each of the following panel families: GEM-P400 / GEM-P800 / Express XP-400 / Express XP-600; GEM-P801; GEM-X255 / GEM-P9600 / GEM-P3200; and GEM-816 / GEM-P1632 / GEM-P1664 / Freedom F-64. Each diagram shows exact terminal-to-terminal wiring between the control panel PC board and the StarLink radio housing, including RJ31X telco connections for backup mode.
This equipment complies with the limits for a Class B Unintentional Radiator, pursuant to Part 15 of the FCC Rules, providing reasonable protection against harmful interference in residential installations. If interference to radio/TV reception occurs, try reorienting the antenna, increasing separation between equipment and receiver, using a different outlet circuit, or consulting a technician.
NAPCO warrants its products free from manufacturing defects in materials and workmanship for 18 months from the date of manufacture — NAPCO will repair or replace, at its option, any product failing to operate correctly, at no charge to the original purchaser. Excludes equipment repaired by others, improperly installed/used, abused, altered, damaged, subjected to acts of God, or with altered/removed serial numbers. No express or implied warranty beyond this description; no warranty of merchantability or fitness for a particular purpose. Any breach-of-warranty action must be brought within 6 months of the warranty period ending. NAPCO is not liable for consequential or incidental damages. To exercise warranty, the product must be returned via the installing security professional, shipping prepaid and insured to NAPCO.
Important: NAPCO recommends the entire system be completely tested weekly. Despite frequent testing, the system may fail to perform as expected due to tampering, electrical/communications disruption, or other factors — NAPCO does not guarantee the system cannot be compromised or that it will prevent injury or property loss. A properly installed and maintained alarm reduces risk but is not insurance or a guarantee against burglary, robbery, or fire.
NAPCO Security Systems, 333 Bayview Avenue, Amityville, NY 11701. Sales/Repairs: (800) 645-9445. Technical Service (security professionals only): (800) 645-9440 or http://tech.napcosecurity.com/