August 31, 2026 5 min read
Full programming instructions for the NAPCO GEM-P1664 Hardwire Control Panel/Communicator.
Full programming instructions for the NAPCO GEM-P1664 Hardwire Control Panel/Communicator, covering both the "classic" GEM-RP2ASe2/RP3DGTL/RP4RFC/RP4C keypads and the "K Series" GEM-K2AS/K3DGTL/K4/K4RF keypads. This manual is written for the professional installer.
Note: The unit is designed to be programmed using an IBM-compatible computer with NAPCO PCD-Windows software (see the separate Quickloader for Windows guide). After programming, always run the PCD-Windows error-check utility to guard against programming conflicts. This page summarizes the keypad-based programming methods; refer to the full PDF for exhaustive location-by-location Direct Address tables.
After entering codes/data, press the U (save) button — data is not stored until saved. If no keypad activity occurs for 4+ minutes in Program Mode, a steady tone sounds; press G to silence and continue, or C to exit. For multi-area systems, use Direct Address Programming Mode to complete setup.
A guided wizard configures: number of zones in Area 1, panel zone doubling (doubles hardwired zone capacity from 8 to 16 for N.C. devices using EZ Zone Doubling™ resistors, if 16+ zones are entered), fire zones (2-wire/4-wire), local vs. Central Station reporting, exit/entry zones (1 and 2), interior follower zones, 24-hour zones, chime zones (1 and 2), 50mS loop response zones (note: 750mS required for UL), Aux output-on-alarm zones, Sensor Watch zones, keypad sounder-on-alarm zones, auto bypass re-entry zones (not evaluated by UL), "no EOLR" zones (not for UL installs), Telco line fault test, CP-01 enable, number of keypads, Central Station phone/account number and receiver format, user codes, RF transmitter points (with Quick Enroll method), key fob transmitters, zone descriptions, dealer code, and test timer.
Once a panel has been programmed by any means, the number of zones is suppressed/locked. To start a new custom default program: from Dealer Program Mode, press C to enter Direct Address Mode, access Location 2285 (Clear Program), press U, and start over.
This mode lets the installer enter data directly at a 4-digit memory address for fine-grained control beyond the Easy Menu wizard.
Press the 0 button to clear the character at the cursor; use NEXT/PRIOR to move between addresses; press G + P to jump to the next programming block. Press C to exit. On GEM-K3DGTL/RP3DGTL and GEM-K4RF keypads, the A button toggles the cursor between the address field and data field, and address contents are read automatically as you type the address.
The full manual's Direct Address section (pages 24-51) covers detailed configuration for: system delays & timeouts, system output timeouts, download/callback options, pager format options, system options, global ambush code, CS (Central Station) receiver/subscriber ID/system/area/zone/user reporting options, EZM group options, area arming and bell control options, keypad options, temperature display at keypad, zone options for zones 1-64 (in four blocks of 16), external relay control, RF receiver & supervisory timer options, and clear program options.
Covers User Code programming only, intended for the end customer (not installer-level access). The Program Mode cannot be accessed while the communicator is transmitting, except during the first 3 minutes after power-up.
Press G0 to clear the character at the cursor; press P or Q to continue to the next entry. This procedure is the same across GEM-K2AS, GEM-K3DGTL, and GEM-K4RF keypads.
Each keypad must be assigned an address number (1-7) and requires its own configuration procedure. For easier zone-description programming, NAPCO recommends using a GEM-RP1CAe2 or GEM-K1CA keypad (see separate NAPCO document WI1422) since the GEM-K2AS/RP2ASe2's reduced display cannot program zone descriptions.
Refer to the accompanying GEM-P1664 Installation Instructions (WI1424) for full wiring diagrams and installation information. This manual is intended for professional installers with suitable experience and installation equipment.
Manufacturer: NAPCO Security Systems, Inc., 333 Bayview Avenue, Amityville, New York 11701. Sales/Repairs: (800) 645-9445. Technical Service: (800) 645-9440. www.napcosecurity.com.