Instruction manual for the Leviton DOS02 (Occupancy/Vacancy) and DVS02 (Vacancy) Single Pole Wide View Motion Activated Light Controls.
Instruction manual for the Leviton DOS02 (Occupancy/Vacancy Sensor Switch) and DVS02 (Vacancy Sensor Switch) — Single Pole Wide View Motion Activated Light Controls, indoor use only. Covers wiring, operation, programming, and troubleshooting.
120VAC, 60Hz — 250W Incandescent, 2A Resistive, 150W LED and CFL, 250VA ELV, 200VA MLV.
The device responds to temperature changes — do NOT mount directly above a heat source, where hot/cold drafts blow directly on the sensor, or where unintended motion (e.g. hallway traffic) falls within the sensor's field of view.
Tools needed: Slotted/Phillips screwdriver, electrical tape, cutters, pliers.
Warning: Turn off power at the circuit breaker or fuse and test that power is off before wiring.
| In order to... | Do this... | Indicator light will... |
|---|---|---|
| Enter programming mode | Hold TOP and BOTTOM button for 5 seconds | GREEN light solid ON for 5 seconds (if nothing happens, already in programming mode) |
| Change settings (Timer, Sensitivity, Ambient Light) | Single press TOP button to advance to next setting | RED light blinks to indicate the setting selected (e.g. Setting 1 = 1 blink/sec) |
| Change options within a setting | Single press BOTTOM button to advance to next option | GREEN light blinks to indicate option selected (Option 1 = 1 blink/sec, Option 2 = 2 blinks/sec, etc.) |
| Save and exit settings | Hold either TOP or BOTTOM button for 5 seconds | GREEN light solid ON for 5 seconds |
If there is no activity for 30 seconds, the device automatically exits programming mode and changes are NOT saved. Multiple settings can be changed and saved in a single programming session.
| Option | Setting 1: Timer (load ON duration since last motion) | Setting 2: Sensitivity | Setting 3: Ambient Light (DOS02 only) |
|---|---|---|---|
| 1 | 1 minute | Low (50% range) | Low light level |
| 2 | 5 minutes | Medium | Medium light level |
| 3 | 10 minutes | High | High/brightest light level |
| 4 | 20 minutes | All settings to default | Disabled — turns ON for all light levels |
Occupancy/Vacancy Switch (DOS02 only): Remove the color kit and wallplate to access the OCC/VAC toggle switch.
| Mode | To Enable | Behavior |
|---|---|---|
| Test Mode | Press and hold TOP of button for 5 seconds. Exit: press TOP or BOTTOM, or auto-exits after 2 minutes. | Turns the load on for 5 seconds each time motion is detected. RED light blinks 1x/2 sec. Locator LED disabled while active. |
| Temporary Bypass Mode (occupancy sensors only) | Press and hold BOTTOM of button for 5 seconds. Exit: press TOP or BOTTOM. | Ignores motion, keeping the light/load off. GREEN light double-flashes every 2 seconds. |
| Programming Mode | Hold TOP and BOTTOM of button for 5 seconds. | GREEN light solid ON for 5 seconds. |
Horizontal field of view: Major motion coverage ~900 sq ft (up to 30 ft), minor motion coverage ~400 sq ft (up to 15-20 ft), depending on angle from the sensor.
Vertical field of view: Effective coverage extends from roughly 40-48 inches mounting height out to 20-30 ft.
Remove the existing color kit cover and replace with the desired color option.
| Issue | Suggested Adjustment |
|---|---|
| Lights don't operate with push pad and RED indicator doesn't blink when motion is present | Verify wiring connections to the sensor. |
| Lights don't switch ON when motion is detected (DOS02) | Motion may be beyond sensing range — move closer to the switch; adjust the light level lower (Option 3/2/1 or disable). |
| RED light blinks (indicating motion) but load doesn't turn on | Could be due to ambient light setting, or check the Occ-Vac switch is in OCC position. |
| Lights always stay ON | Check time delay settings vs. actual on-time; confirm no motion occurs in the coverage area for the selected time by covering the lens; check the switch isn't near a heat source or detecting motion from an adjacent area (e.g. hallway traffic) — relocate if so. |
| Lights don't turn ON (DVS02) | Make sure the control is installed correctly, power is ON, and the light bulb is functional. |
This device complies with Part 15 of the FCC Rules. Operation is subject to two conditions: it may not cause harmful interference, and it must accept any interference received, including interference that may cause undesired operation. Tested and complies with Class B digital device limits under Part 15, providing reasonable protection against harmful interference in residential installations. If interference occurs, try reorienting the antenna, increasing separation, using a different circuit outlet, or consulting a technician. Unauthorized modifications could void the user's authority to operate the equipment.
Limited 5-Year Warranty. For full warranty details, visit www.leviton.com, or call 1-800-824-3005 for a printed copy. Patents at www.leviton.com/patents.
Technical assistance: 1-800-824-3005 (USA) or 1-800-405-5320 (Canada). Canadian warranty/returns: Leviton Manufacturing of Canada Ltd, Quality Assurance Department, 165 Hymus Blvd, Pointe-Claire (Quebec), Canada H9R 1E9.