Installation and startup guide for the GE Security NetworX NX-590E Internet Interface module — connects NX security panels to receivers and email over the network.
Installation and startup guide for the GE Security NetworX NX-590E Internet Interface — a module that connects NetworX (NX) series security control panels to a central monitoring receiver or email accounts over the Internet/Intranet.
The NX-590E is a dual microprocessor-controlled Internet/Intranet interface that connects to an OH Network Receiver, allowing any or all events from a NetworX control panel to be reported over the network. It attaches to the NX control panel's keypad bus, has a fixed module address of 79, and requires an Ethernet (10BT) connection.
Inside the enclosure, black plastic PCB guides mount at insertion points (two hole sizes: a larger hole for the half-moon protrusion, a smaller hole for the mounting screw). Place the first guide in the top insertion point (grooved edge down), secure with a screw through the length notch; place the second guide in the lower insertion point (grooved edge up) the same way. The PC board should then slide freely in both guides.
The Internet module has a fixed address of 79. Enter this address when selecting the module to program.
NetworX control panels automatically detect and enroll all devices on the keypad bus (keypads, zone expanders, wireless receivers, etc.) when Program Mode is exited. Enrollment takes about 12 seconds, during which the "Service" LED illuminates (LCD keypads show "Service Required") and user codes are not accepted. If the control panel later fails to detect an enrolled module, the Service LED illuminates again.
| LED | Description |
|---|---|
| DS1 | Flashes each time the NX-590E accesses the NetworX bus (~2x/sec). |
| DS2 (rear of board) | Hardware use only; glows dimly when connected to an NX8/NX8-E control. |
| DS3 | Flashes when waiting for communication from the Ethernet module. |
| DS4 | On when waiting for a reply from a NetworX bus device. |
| DS5 | Flashes when the NX-590E gets a packet from the Ethernet module. |
| DS6 | On when the bus has a message to send to the network. |
| L1 (SIM module) | Flashes on Ethernet activity. |
| L2 (SIM module) | Steady on when Ethernet link is established via the 10BT cable. |
DS3–DS6 will be off when the system is initialized, normal, and waiting for a new event to report.
Wire the 3-position terminal on the module to the NX control: Positive to KP POS, COM to KP COM, DATA to KP DATA. Connect the Ethernet jack J16 (10BT) to a 10BT-capable hub, router, or gateway — do not use a CASCADE or X port in crossover mode.
| Max wire run length (ft) | 250 | 500 | 1000 | 2000 | 2500 |
|---|---|---|---|---|---|
| Connected to NX-8 / NX8-E | 22 | 20 | 16 | 14 | 12 |
| Connected to NX-320E | 22 | 18 | 16 | 12 | 12 |
(Values shown are AWG wire gauge required for each run length.)
| Terminal | Description |
|---|---|
| POS | Connect to panel's KP POS terminal. Current draw: 100mA for the NX-590E. |
| COM | Connect to panel's KP COM terminal. |
| DATA | Connect to panel's KP DATA terminal. |
| J16 | Connect to a 10BT network hub via CAT5 patch cable. |
| J6 | Connect to an RS-232 modem when the unit ships with serial software. |
Factory Defaulting: enter [9]-[1]-[0]-[#] — the keypad beeps 3 times as defaults load (this erases any previously entered values).
Programming a Location: enter the location number + [#]. Enter data followed by [*] to save each segment and advance; press [#] to exit the location. Use [POLICE] for the next sequential location, [FIRE] for the previous location, or [AUXILIARY] to stay on the same location. Invalid entries trigger a triple error beep.
LCD Keypad: works the same way, with on-screen prompts. A location number in parentheses reminds you of the last location you edited.
| Location(s) | Purpose |
|---|---|
| 0 | Module mode: backup dialer, SIA vs. Contact ID, DHCP vs. static IP, AA polling enable, remote/site-initiated downloading. |
| 1 | Which partitions report via Internet to Receiver #1 (16 event-type segments: alarms, open/close, bypass, zone trouble, power trouble, siren/phone fault, test reports, tampers, etc.) — factory default: all partitions on. |
| 2 | Same event-type segments, for Receiver #2 — factory default: all partitions off. |
| 3 | Same event-type segments, for Email Account #1 — factory default: all partitions off. |
| 4 | Same event-type segments, for Email Account #2 — factory default: all partitions off. |
| 13–16 | This module's return email address (user@yourdomain.com), 16 characters per location, 4 locations total (64 chars max). |
| 29–36 | Destination email addresses (Account #1: 29-32, Account #2: 33-36) — must be real, working addresses. |
| 37–40 | Outgoing mail server name (e.g. mail.yourdomain.com) — confirm the server accepts mail from the NX-590E's domain. |
| 45–52 | IP addresses (required if using static IP instead of DHCP): 45 = this module, 46 = primary receiver, 47 = secondary receiver, 48 = on-site event recorder, 51 = mail server, 52 = gateway. Power-cycle the module after changing IP settings. |
| 53 | Download computer's IP address (default 0.0.0.0). |
| 54 | Subnet mask (typically 255.255.255.0) — confirm with your network administrator. |
| 55–57 | TCP/IP ports: Receiver Alarm Port (55), Receiver Download Port (56), Email Port (57, default 025) — only change on your central station provider's instruction. |
| 60 | SIA or Contact ID account number (8-digit hex; add leading zeros). |
| 61–62 | Phone line receiver number and line number for this account. |
| 63 | Timers/counters: Segment 1 = network attempt count (default 2), Segment 2 = seconds per overall attempt (default 30, min 30), Segment 3 = polling time in seconds (default 10). |
Important: if the NX-590E is set as the primary reporting device (with the control panel as backup only), disable all event categories in Location 4 of the control panel (device 0) to avoid dual reporting — but keep test reports enabled there so the panel can back up events the NX-590E fails to send. Note the NX-4 and NX-6 (V1) control panels cannot act as a backup to the NX-590E.
| Operating power | 12VDC, supplied from NX-4, NX-4V2, NX-6, NX-6V2, NX-8, NX-8V2, NX-8E, or NX-320E |
| Current draw | 120mA during communication, 90mA standby |
| Operating temperature | 32°F to 120°F |
| Dimensions | 6.0"W x 3.25"H x 1.0"D |
| Shipping weight | 1 lb. |
Tested and found to comply with Class B digital device limits under FCC Rules Part 15 — this equipment may not cause harmful interference and must accept any interference received, including interference that may cause undesired operation. Designed to provide reasonable protection against interference in residential installations; if interference to radio/TV reception occurs, try reorienting the receiving antenna, increasing separation between the equipment and receiver, connecting to a different circuit, or consulting an experienced technician. Changes or modifications not expressly approved by the manufacturer could void the user's authority to operate the equipment. This Class B digital apparatus complies with Canadian ICES-003.
CE-marked products: Model NX-590E (TCP-IP Internet module), manufactured by GE Interlogix, 1420 N Main, Gladewater, TX 75647 USA, complies with EMC Directive 89/336/EEC and Marking Directive 93/68/EEC per applied standards EN50130-4 (1995)+A1(1998) and EN50081-1(1992)/EN55022:1998+A1(2000).
GE Security. Main: 800-727-2339. Outside the US: 903-845-6941. Technical Support: 888-432-3287. Sales & Literature: 800-547-2556. Main Fax: 903-845-6811. Web: www.ge-security.com