September 08, 2026 2 min read
Installation guide for the ELK-M1DBHR Data Bus Hub Retrofit, which splits a single M1 RS-485 data bus into 4 managed branches for retrofit jobs with limited existing wiring.
The ELK-M1DBHR Data Bus Hub Retrofit is designed for retrofit jobs where existing 4-conductor cables are the only wires available. It creates 4 managed RS-485 branches from a single M1 main RS-485 data bus, allowing up to 2 home-run cables per branch (4 branches x 2 each = 8 home runs total).
Mount the M1DBHR inside the main M1 Control enclosure and connect it to the M1's Data Bus terminals (+VKP, DATA A, DATA B, NEG) using a short 4-conductor cable. The M1DBHR provides 5 terminating jumpers:
| Jumper | Function |
|---|---|
| JP1 | Terminates input from the M1 Control |
| JP2 | Terminates Branch 1 |
| JP3 | Terminates Branch 2 |
| JP4 | Terminates Branch 3 |
| JP5 | Terminates Branch 4 |
The examples above illustrate the flexibility of the 4 data-bus branches; the actual number and type of devices used on each branch is up to the installer.
Do NOT connect +VKP to the M1DBHR if it's being powered from an auxiliary power supply. When adding additional data bus devices, calculate the total current draw — if it exceeds the M1 Control's limits, add an auxiliary 12VDC power supply. Connect all Negative (-) wires together to form a common negative reference path.