September 08, 2026 5 min read
Installation and operation manual for the ELK-P212S Supervised Remote Power Supply / Battery Charger, covering stand-alone and M1 Data Bus wiring, jumper settings, zone/output assignment, and diagnostics.
The ELK-P212S is a Supervised Remote Power Supply / Battery Charger providing 12VDC output with up to 2 Amps of total current. It supervises AC power input and rechargeable battery status, reporting abnormal conditions back to an ELK M1 Control over the RS-485 4-wire data bus, or can be used stand-alone with any other Control (Security, Access, CCTV, etc.).
Power from the P212S can increase a control's capacity or remotely power devices such as motion detectors, keypads, zone expanders, sirens, and annunciators. Decentralized placement of expanders and other devices into strategic wiring closets, each with its own local supervised power supply, reduces wire home-runs and simplifies maintenance.
| AC Input | 16.5VAC, 45VA (ELK-TRG1640 or equivalent) |
| DC Output Voltage | 13.8 VDC ± 5% |
| Current Rating | 2.0 Amps |
| Wattage | 30 Watts |
| DC Output Protection | Auto-resetting PTC |
| Rechargeable Battery Size | Max. 12 Ah |
| Low Battery Cutoff Threshold | ~10 Volts |
| Load Regulation | ±2% |
| Part Number | Description |
|---|---|
| ELK-TRG1640 | Transformer, 16.5VAC 40VA w/PTC Protection |
| ELK-1280 | Battery, 12VDC 8Ah |
| ELK-W018B | 4-conductor ribbon cable for local connection of input/output expander modules |
| ELK-UB12 | Metal Enclosure, 12" x 12" x 3.25" |
| ELK-SWP3 | Mounting Plate for Structured Wiring Enclosures |
In stand-alone mode the P212S is compatible with virtually any control or annunciator. It provides two Form "C" relay outputs for AC and Battery supervisory notification. When AC and Battery are normal, the relays are energized and the Com/N.O. contacts are CLOSED. Upon an AC failure or Low Battery condition, the relay changes state — Com/N.O. contacts OPEN and Com/N.C. contacts CLOSE. This flexibility lets the P212S interface with any alarm panel requiring an open or closed trouble indication.
AC Time Delay (JP2): The AC Trouble output has a built-in delay after loss of AC to avoid nuisance trips from brief outages. Jumper JP2 selects 5 or 15 minutes of delay (short left two pins = 5 min; right two pins = 15 min).
Testing on battery only: The low-battery shutoff circuitry normally prevents power-up on battery alone (no AC). For testing at construction sites with no AC available, momentarily short the two "START" circuit pads with a screwdriver tip.
The P212S connects to the M1's 4-wire RS-485 Data Bus and enrolls as a "Type 1" Keypad device with a Bus Address. It's enrolled as a keypad so it can have a zone input (for AC/Battery supervisory reporting) and a programmable output, just like a real keypad — though it does take up one of the M1's maximum 16 keypad slots.
The P212S needs only THREE connections to the M1 data bus: Negative (-), Data A, and Data B. The incoming Positive (+) red wire should be terminated ("parked") on the isolated "Spare" terminal rather than connected — never connect the Positive (+) wires of multiple power supplies together (it's fine to tie all Negative wires together).
Set via a 4-gang binary switch (values 1, 2, 4, 8) before enrollment. Example: switches 1 & 3 ON = address 5 (1+4). All switches OFF = address 16. Each address must be unique — do not duplicate an address already used by an enrolled keypad.
Type 1, Address 1 → Zone 193 / Output 193, through Address 16 → Zone 208 / Output 208 (sequential).
Note: ElkRP software won't display Zones 193-208 until a Hardwired Exp. 13 zone group has been added — right-click Zones (Inputs), select New Hardwired Zones, choose "Zones 193-208 (Group 13)."
Battery Autotest Timing: Initial test 1.5 minutes after power-up, then every 4 hours. On the M1 bus, the P212S syncs its test time with the M1's main battery test, offset by minutes equal to its bus address (staggers multiple units). When AC is off, testing occurs every minute.