August 31, 2026 5 min read
System installation manual for the AprilAire Model 8800 Communicating Thermostat network with Model 8819 Distribution Panel.
System installation manual for the AprilAire Model 8800 Communicating Thermostat system — covers wiring and checkout for a networked RS-485 thermostat system using the Model 8819 Distribution Panel and Model 8811 Protocol Adapter.
This manual guides installers through installation, wiring, and checkout of an AprilAire Model 8800 Communicating Thermostat System. For a complete command set and programming suggestions, see the separate programming manual (Part No. 10009414) at www.aprilairepartners.com/docs/literature.
Warning: 120 volts may cause serious injury from electrical shock — disconnect electrical power to the HVAC system before starting installation (this is a low-voltage system). Installation must be performed by a qualified contractor per NEC standards and applicable local/state codes.
Disconnect power at the zone control panel input terminals (if zoned) or at the HVAC equipment disconnect switch / breaker / fuse. Caution: Failure to disconnect power could damage HVAC equipment or thermostats — leave power off until all connections are made and verified.
Determine component locations, run and label wires (thermostat cable for HVAC control wiring, CAT-5 for the communication bus, straight-through serial cable for the protocol adapter), then mount each component per its own installation instructions.
| From | To | Maximum Distance |
|---|---|---|
| Automation/Computer System | Protocol Adapter | 3 ft. (cable provided) |
| Protocol Adapter | Thermostat (incl. through Distribution Panel) | 4000 ft. cumulative |
| Thermostat | Support Module | 1000 ft. cumulative |
| Support Module | Temperature Sensor Option | 300 ft. |
| Thermostat | Temperature Sensor Option | 300 ft. |
A network interconnection worksheet is provided in the manual to record job title, location, date, contractor, and each thermostat's CAT-5 wire run and location address — fill it out and leave it with the system software package.
A qualified HVAC technician should perform this step. Make sure HVAC power is off, then wire per the Thermostat Installation Instructions' diagrams for conventional heat/cool, heat pump, and humidistat configurations. Thermostat terminals include: B+ A+ B- A- C B O Y Y2 G RC RH W2 W R S2 S1 T1 T2 RSB RSA.
Do not turn on HVAC system power yet — communication wiring comes next.
If more than one Distribution Panel is used, daisy-chain the communication lines together using consistent wire colors, and power each panel with its own separate Model 8029 24VAC transformer (or equivalent 40VA 24VAC transformer). Ensure all panel switches are off before wiring.
RS-485/422 DB9 connector pinout: Pin 1 = A-, Pin 2 = A+, Pin 3 = B-, Pin 4 = B+, Pin 5 = GND, Pin 7 = +9V (Tx-/Tx+/Rx-/Rx+ signal roles vary by pin).
Use the thermostat's own checkout procedure (in its installation instructions) to confirm equipment control before verifying the communication network.
To reset installer settings to default, press the RESET button inside the thermostat's battery cover.
The original manual documents using Windows HyperTerminal (Windows 95/98/2000/NT/XP) connected via the Protocol Adapter's RS-232 port to verify communication. Key serial settings: 9600 bps (or 19200 if thermostats are configured for that rate), 8 data bits, no parity, 1 stop bit, no flow control. Typing a character should flash the Protocol Adapter's RXD LED, confirming the link. This legacy PC utility is superseded on modern systems by the automation controller's own diagnostics — consult your automation system's documentation for current checkout procedures.
Special wiring applies when installing the Model 8800 alongside the 8870 Series Communicating Thermostat via a Model 8818 Distribution Panel, including dedicated RSR/RSC/RSB/RSA and T1–T4 terminal connections through an 8061/8062 support module. See the original PDF for the full interconnect diagram.
Four-sensor or nine-sensor temperature averaging is supported without support modules, using 2-wire thermostat cable (R=red, W=white) wired to the thermostat's S1/S2 (four-sensor) or S1–S9 (nine-sensor) terminals. Works with Model 8051 flush-mount or Model 8053 surface-mount sensors (same wiring for both).
AprilAire (Research Products Corporation), P.O. Box 1467, Madison, WI 53701-1467. Phone: 800-334-6011. Fax: 608-257-4357. www.aprilairepartners.com.