  • Winland WaterBug WB-200 — Installation & Operating Instructions

    August 31, 2026 3 min read

    Complete installation and operating instructions for the Winland WaterBug® WB-200 electronic water detection device.

    Full text manual (for reference)

    Complete installation and operating instructions for the Winland WaterBug® WB-200 electronic water detection device.

    Overview

    The WB-200 is a fully electronic water leak detector designed to detect the presence (or absence) of water only — it cannot detect distilled or deionized water. It is not a self-contained warning device: it must be used in conjunction with an alarm system, sounder, or other signaling device. The control console mounts on a wall or other flat vertical surface, and up to 6 remote probes can be wired in parallel to the two "sensor" terminals, placed wherever water leakage is most probable. A thin film of moisture bridging the two metallic contacts on any probe is enough to trigger an alarm. The output is non-latching and resets automatically once the probe dries and the moisture bridge is broken. The WB-200 will not false-alarm due to high humidity or condensation, making it suitable for homes, offices, computer rooms, warehouses, and similar spaces.

    What's in the Box

    • 1x WB-200 console
    • 1x Surface Probe – Unsupervised (W-S-U)
    • 1x Installation/Operating Instructions Guide

    Installation

    1. Locate the mounting area for the WB-200 console and use the unit as a guide to mark the two mounting-flange hole locations.
    2. Drill the holes. If mounting on drywall, use the provided drywall anchors.
    3. Position the WB-200 against the surface and drive the screws into the holes or anchors.
    4. Wire multiple probes in parallel to the two "sensor" terminals (up to 6 total per console).
    5. Mount remote surface probes securely to the floor or a wall. Mounting to a vertical surface lets you monitor for rising water levels — useful for basement sump pumps and other drainage/storage systems.

    Terminal Block Connections

    Relay contacts are accessible on the terminal block: VAC/+VDC, Ground (VAC/−VDC), Relay N.C., Relay N.O., and Relay Common. The WB-200 is in normal condition when power is applied and no moisture is detected; it enters alarm condition when water is detected at any connected probe.

    • AC power: input wires are interchangeable.
    • DC power: positive to V+, negative to Ground — observe polarity, since incorrect polarity will prevent proper operation.

    Standard Surface Probe (Unsupervised)

    If bolting a remote probe down for a permanent installation, drill only in the innermost center recessed area. Drilling anywhere else may damage internal wiring and cause the WB-200 to fail. Ensure the four stainless steel probe contacts are firmly against the surface being monitored.

    Monitoring for the Absence of Water

    The WB-200 can also monitor for the absence of water (i.e., a minimum water level) by mounting the probe at the desired minimum waterline and using the opposite set of relay contacts you'd use to detect the presence of water. Test weekly to ensure proper operation.

    Note: Concrete can be semi-conductive. If you experience false alarms, insulate all probes mounted on concrete.

    Test Procedure

    To test operational status, form a water bridge between the two metallic contact points on a probe using a moistened finger or cloth. If working properly, the WB-200 will activate the connected warning device within approximately three seconds, and will reset automatically once the probe dries and the moisture bridge is broken.

    Specifications

    Power Requirement 8–28 VDC @ 35mA, or 8–28 VAC @ 100mA
    Sensitivity Will not alarm due to high humidity or condensation
    Operating Temp 32° to 130°F (0° to 54°C), non-condensing, indoor use only
    Output 1 Form C Relay (N.O./N.C.) — 1 Amp @ 30 VDC resistive, 1 Amp @ 24 VAC resistive
    Probe Options Includes 1 Standard Unsupervised Surface Probe (W-S-U); accepts up to 6 Unsupervised Surface (W-S-U) or Under Carpet (W-UC-U) probes wired in parallel
    Max Cable Length 1–2 probes: 200' (61 m) max; 3–6 probes: 100' (30.5 m) max
    Probe Cable 15" (4.6 m) cable included; extend using 22–18 AWG twisted pair
    Console Weight / Dimensions 2.4 oz (0.07 kg); 4.1 x 2.36 x 1.18" (10 x 6 x 3 cm) with flanges
    Probe Dimensions Surface: 2 x 3 x 0.88" (5.1 x 7.6 x 2.2 cm); Under Carpet: 2 x 3 x 0.18" (5.1 x 7.6 x 0.5 cm)
    Mounting Flanges
    Case Material ABS
    Warranty 1 Year Limited

    Warranty

    Winland Electronics warrants the WB-200 against defects in materials and factory workmanship for one year from the date of purchase when properly installed and operated under normal conditions. Winland's obligation under this warranty is limited to correcting, without charge, any part returned to the factory (transportation prepaid) that is found to have been originally defective. This warranty does not apply to products subject to misuse, negligence, accident, or unauthorized repair/alteration, and is void if the product housing is removed.

    Support

    Winland Electronics tech support: (800) 635-4269 or +1-507-625-7231, 8:00am–5:00pm Central Time. www.winland.com