Installation Manual for the SECO-LARM ENFORCER SD-995C / SD-994C Electric Door Strikes (12VDC/24VDC) — field-programmable fail-safe/fail-secure electric strikes for metal and wood doors.
Full Installation Manual for the SECO-LARM ENFORCER® SD-995C (12VDC, metal doors) and SD-994C (12VDC, wood doors) Electric Door Strikes, also covering the 24VDC versions SD-995C24 and SD-994C24 — field-programmable for fail-safe or fail-secure operation, converting cylindrical lock sets into an electronic access-controlled locking system.
| Spec | Value |
|---|---|
| Metal door dimensions (ANSI-sized) | 4-7/8" x 1-1/4" x 1-1/4" (124 x 32 x 32 mm) |
| Wood door dimensions | 7-15/16" x 1-7/16" x 1-1/4" (202 x 36 x 32 mm) |
| Current draw | 250mA @ 12VDC; 150mA @ 24VDC |
| Jaw strength | 2,000 lbs. |
Note: SD-995C and SD-994C are mounted the same way.
Align and tape the template on the door jamb to the latch line and the center line.
Cut into the door jamb as shown on the template, to a depth of 17mm. Discard the metal cut out. For wood doors, use a chisel to knock out a 3mm (1/8 inch) deep space as shown on the template.
Double-check the cut by placing the unit in the hole and confirming a proper fit; make any adjustments needed.
Using the two small (M4x12) screws and two of the black clips provided, fix the mounting tabs to the inside of the jamb.
The unit can be programmed for fail-secure operation (door locked when power is lost or cut) or fail-safe operation (door unlocked when power is lost or cut). Default is fail-secure.
To program for fail-safe: remove the flat screw in the fail-secure hole, push the round screw to the right until a hole appears in the fail-safe hole, then screw the flat screw into the fail-safe hole.
Connect the two wires to the access control or egress device, such as a digital keypad, push-button switch, push bar, or other device. Polarity is not important. Insulate the wire connections carefully.
Push all the wires into the door frame. If needed, cut away the dust catcher inside the frame, or carefully chip away part of the drywall (being careful not to damage the wall). Use the two large (M5x12) screws to mount the unit to the mounting tabs. Adjust as needed to ensure the door closes smoothly every time someone passes through the protected opening.
ENFORCER Electric Door Strikes are warranted against defects in material and workmanship under normal service for a period of one (1) year from the date of sale to the original customer. SECO-LARM's obligation is limited to the repair or replacement of any defective part if the unit is returned, transportation pre-paid, to SECO-LARM.