Full installation and programming manual for the Seco-Larm ENFORCER SA-027WQ 7-Day Timer, a programmable relay timer for security, access control, lighting, and environmental control.
Installation and programming manual for the SECO-LARM ENFORCER SA-027WQ 7-Day Timer, a programmable relay timer for security, access control, lighting, and environmental control applications.
The SA-027WQ can be programmed to operate a Form C relay 24 hours a day on a weekly basis, with up to 60 events on a weekly or daily schedule. A programmable holiday disables the timer for a single day weekly.
1x Timer, 2x mounting screws, 1x manual.
| Spec | Value |
|---|---|
| Operating voltage | 10-48 VDC / 12-24 VAC |
| Number of relays | One (1) Form C |
| Relay contact rating | 10A@14VDC |
| Relay active current draw | 110mA@12VDC ±10% |
| Standby current draw | 14mA@12VDC ±10% |
| Event capacity | 60 events |
| Operating temperature | -4° to 167°F (-20° to 75°C) |
| Dimensions | 4 1/8" x 3" x 15/16" (105 x 76 x 33 mm) |
| Weight | 5.6 oz (158g) |
Diode/varistor requirement: to protect the relay, install a 1N4004 diode (cathode/striped end wired toward the positive side, not included) in parallel with the power supply, as close to the lock as possible, for DC-powered locks — unless the lock has a diode built in. AC-powered locks and electromagnetic locks require a varistor/MOV (05D390K or similar, not included) in the same location if not already built in (all SECO-LARM electromagnetic locks have built-in protection). Failure to use these as directed will void the warranty.
First-person-in (FM) function: suspends timer operation when its optional N.O. switch is activated. If the corresponding relay is on before the FM switch is activated, the relay stays on until the FM switch deactivates — the timer then resumes the last programmed function.
The timer can be programmed before installation. EEPROM memory protects programming through power failures; the super capacitor (after a full 24-hour charge) preserves date/time for 7-10 days after power loss.
| Menu | Description |
|---|---|
| Set Events | Set timed events (up to 60), including event number, relay operation, day and time. Supports block programming. |
| Set Holiday | Program a holiday event — a day when normal timer operation is suspended. |
| Set PinCode | Set a 4-digit PIN code to secure the timer (optional, factory default 0000). |
| Set Time | Set current day and time (24-hour/military format). |
| Set DST | Disable (standard time) or Enable (adds 1 hour). |
| System Test | Shows current relay status and allows toggling to test relay operation. |
| Set Display | Adjust display contrast (relative values 00-09). |
| Clr Memory | Clears all programmed items except the PIN code (requires yes/no confirmation). |
General flow: press SEL to cycle to the desired menu, ENTER to open it, ENTER to change the flashing option, SEL to accept and move to the next field, and ENTER on the Return icon to save and exit to the home screen.
Navigate to Set Display, press ENTER, then repeatedly press ENTER to cycle contrast from 00 (default) to 09 (cycles back to 00). Alternatively, press and hold SEL + ENTER together at any time to gradually adjust contrast; release when satisfied.
Navigate to Set Time; the day flashes first — press ENTER to change, SEL to accept and move to the next field (time). Time is displayed in 24-hour/military format (1:00 PM = 13:00:00).
Navigate to Set DST; press ENTER to toggle Enable/Disable, SEL to accept. Disable = standard time; Enable = adds one hour.
Forgot your PIN? Turn off power and disconnect the backup battery. Power the timer back on and immediately press and hold ENTER for at least 3 seconds until the lock icon disappears — this resets the PIN to 0000.
Navigate to System Test, press ENTER to see the current relay state (e.g. R1=OFF), then press ENTER again to toggle the relay — pressing again toggles it back.
Navigate to Clr Memory, press ENTER, then toggle between NO and YES with SEL. Selecting YES and pressing ENTER clears all programmed items (except PIN code) after 3-5 seconds.
| Issue | Solution |
|---|---|
| How can I test that a relay is working? | Use System Test to toggle the relay on and off. |
| Unsure my device is receiving correct input voltage | From the home screen, press ENTER to view the input voltage. |
Users and installers are responsible for ensuring installation and configuration comply with all national, state, and local laws and codes. California Proposition 65: these products may contain chemicals known to the State of California to cause cancer, birth defects, or other reproductive harm (see www.P65Warnings.ca.gov).
Warranty: warranted against defects in material and workmanship for one (1) year from the date of sale to the original customer, under normal service. SECO-LARM's obligation is limited to repair or replacement of defective parts (transportation prepaid to SECO-LARM). Void if damage results from acts of God, misuse/abuse, neglect, unauthorized repair/alteration, improper usage, or faulty installation. SECO-LARM is not liable for special, collateral, incidental, or consequential damages.
SECO-LARM U.S.A., Inc., 16842 Millikan Avenue, Irvine, CA 92606. Phone: (949) 261-2999 / (800) 662-0800. Email: sales@seco-larm.com. Website: www.seco-larm.com.