August 31, 2026 4 min read
Complete installation and operation manual for the RCS TZ45 Z-Wave Thermostat, covering Z-Wave setup, HVAC wiring, and installer configuration.
Installation and Operation Manual for the RCS TZ45 Z-Wave Thermostat — covers HVAC configuration, Z-Wave network setup, user operation, and wiring for standard and heat pump systems.
| Product | Thermostat for Heating and Cooling HVAC systems, Z-Wave RF enabled |
| Size | 5.7" W x 4.0" H x 1.2" D |
| Display | Graphical LCD, 2.75" x 1.5", 64x128 pixel |
| Backlight | Blue/white, controllable (on / off / timeout) |
| Buttons / LEDs | 6 buttons, 4 LEDs (3 green, 1 red) |
| Power | 24VAC from HVAC system |
| Temperature Sensing Range | -40°F to +190°F |
| HVAC Compatibility | Standard (gas/electric) or Heat Pump |
| Multistage — Standard | 2-stage heating, 2-stage cooling |
| Multistage — Heat Pump | 3-stage heating (2 compressor + 1 aux heat), 2-stage cooling |
| Remote Sensors | 2 connections, 2-wire, primary or averaging |
| Communications | Z-Wave RF |
The TZ45 supports the Z-Wave Thermostat General V2 device class, compatible with most Z-Wave controllers. To add it to a network:
Verify success by checking the ZHID (Home ID) and ZNID (Node ID) in the Thermostat Info screen — an un-configured thermostat shows zeros for both. Setback Mode: controllers without full thermostat device class support can still trigger the energy-saving AWAY mode via BASIC_SET commands (0x00 = AWAY mode using predefined setback setpoints; 0xFF = revert to prior mode).
The main screen displays current room temperature, heating/cooling setpoints, system mode, fan mode, time, and status. A "Minimized Display Mode" can be enabled in User Settings to show only the temperature after a configurable timeout (0 = disabled).
Press Up or Down on the main screen to open the current mode's setpoint screen and adjust in 1-degree increments (press and hold for continuous change). Setpoint range: 50°F-90°F (4°C-32°C) heating, 55°F-99°F (10°C-37°C) cooling. The thermostat maintains a minimum 3-degree separation between heating and cooling setpoints, automatically "pushing" the other setpoint if you try to violate that separation. If System Mode is OFF, pressing Up/Down takes you to the System Mode screen first.
| Setting | Range | Default |
|---|---|---|
| Display Lock | Y/N | N |
| F/C Mode | C or F | F |
| Screen Timeout | 0, 20-120 sec | 0 |
| Schedule Enable | Y/N | N |
| Max Heat Setpoint | 50-90°F (4-32°C) | 90°F |
| Min Cool Setpoint | 55-99°F (10-37°C) | 55°F |
| Min Run Time (MRT) | 1-9 min | 3 |
| Min Off Time (MOT) | 5-9 min | 5 |
| Mechanical Type | Std or HP | Std |
| Fan Type | Gas or Elec | Gas |
| Changeover Type | w/Heat or w/Cool | w/Cool |
| H/C Setpoint Delta | 3-15 | 3 |
| Fan Cycler ON/OFF Time | 0-120 / 10-120 min | 0 (off) / 10 |
Set Mechanical Type to Gas/Elec (default). Set Fan Type to GAS for gas systems (no fan output required for heat) or ELEC for electric/hydronic systems (fan output required with heat call). Single-stage systems use W1 (heat) and Y1 (cool); two-stage heating adds W2, two-stage cooling adds Y2 (both must be enabled in Installer Settings). For a single, shared transformer, do not cut jumper JP1 — wire the HVAC's 24VAC common (blue) to 24Com and 24VAC return (red) to either 24RH or 24RC. For separate heating/cooling transformers, cut JP1: wire heating 24V R to 24RH and cooling 24V R to 24RC, with cooling 24VAC common to 24COM.
Set Mechanical Type to Heat Pump (Fan Type is then set automatically). Single-stage compressor systems use Y1 for stage-1 heat/cool and W1 for aux heat (heat strips); two-stage systems add Y2, with W1 as stage-3 aux heat. Configure the Changeover Valve type to match your system: O (orange wire) = changeover with cooling (default, most common), B (brown wire) = changeover with heating — if you get cooling when expecting heat, flip this setting. Heat pumps use a single transformer — do not cut the RC/RH jumper.
Compatible with RTS3 and RTS4 two-wire remote sensors via shielded twisted-pair cable (connect shield to 24VAC Com).
MRT keeps the system running after a heat/cool call starts, even if the setpoint is satisfied early, to ensure even cycles (changing mode to OFF cancels MRT immediately). MOT enforces a delay (minimum 5 minutes) between cycles to protect compressors from short-cycling. Both are adjustable in Installer Settings, and their active status shows on the System Status LED label.
FCC Part 15 Class B compliant. Complies with Industry Canada license-exempt RSS standards. Unauthorized modifications may void FCC compliance authority.