August 31, 2026 6 min read
Full installation guide for the RISCO WatchOUT Dual Technology Outdoor Detector (RK315DT), covering Relay Mode and ProSYS BUS Mode installation.
Complete installation guide for the RISCO WatchOUT Dual Technology Outdoor Detector (RK315DT series), covering both standalone Relay Mode and ProSYS BUS Mode installation, mounting, DIP switch settings, lens types, and diagnostics.
The WatchOUT is an outdoor intrusion detector combining two Passive Infrared (PIR) channels and two Microwave (MW) channels for reliable detection with reduced false alarms. It can operate as a standard relay detector connected to any control panel, or as a BUS accessory connected to a RISCO ProSYS control panel via RS485, gaining remote control and diagnostic capability.
Changing back tamper position: the back tamper defaults to the right side (rear view). To move it to the left: remove tamper screw 1, confirm tamper spring rests over the tamper wire base, confirm the plastic tamper bracket rests over both, then re-secure the screw into the new position. Listen for an audible "click" when the tamper spring engages the wall. For pole installations, the tamper can be relocated to the bottom right of the internal base.
| Terminal | Function |
|---|---|
| +, - | 12VDC power input |
| ALARM | N.C. relay, 24VDC, 0.1A |
| FREE / FREE YEL | Free pins for connecting wires and EOL resistors |
| TAMPER | N.C. relay, 24VDC, 0.1A |
| AM | N.C. relay output (24VDC, 0.1A) indicating Anti-Masking alarm or detector trouble (excludes dust/dirty lens). If a vibration detector is installed and DIP8 is enabled, this relay also opens momentarily on a vibration event. |
| LED | Remote control of LEDs when DIP1 is ON |
| ENABLE | +12V or no connection = enabled; 0V = disabled |
| DUST | N.O. open collector, 70mA max — indicates a dirty lens requiring cleaning |
| TEST | Apply 0V for remote alarm test; success = Alarm relay opens momentarily; failure = AM relay opens |
| SET/UNSET | Controls Anti-Masking and LED behavior based on system arm state — while armed, this hides detector status from an intruder and disables Anti-Masking indication. |
| DIP | Function | On / Off |
|---|---|---|
| DIP 1 | LEDs operation | On = Enabled; Off = Disabled |
| DIP 2-3 | Detection sensitivity | Off/Off = Low; Off/On = Mid; On/Off = Normal (default); On/On = Maximum (disables sway recognition) |
| DIP 4 | Alarm condition logic | On = PIR or MW (OR logic); Off = PIR + MW (AND logic) |
| DIP 5 | Detector optics | On = Barrier/Long range; Off = Wide angle |
| DIP 6 | LED display mode | On = Red LED only; Off = 3 LEDs |
| DIP 7 | Anti-masking | On = Enabled; Off = Disabled |
| DIP 8 | Vibration detection (units with vibration sensor) | On = Enabled; Off = Disabled |
Adjust the microwave coverage using the trimmer on the PCB. Two minutes after applying power, walk-test the protected area to verify proper operation. On uneven surfaces, slide the PCB inside the internal base to the height marking that matches your installation (1.0m, 1.5m, 2.2m, or 2.7m, printed on the PCB), or use the standard swivel accessory. To reduce detection range, slide the PCB up or tilt the swivel down.
| LED | State | Meaning |
|---|---|---|
| Yellow | Steady | PIR detection |
| Yellow | Flashing | Anti-mask (AM) detection |
| Green | Steady | Microwave detection |
| Red | Steady | Alarm |
| Red | Flashing | Malfunctioned communication with ProSYS (BUS mode only) |
| All LEDs | Flashing sequentially | Unit initialization on power-up |
DIP 1 must be ON to enable LED indications. Only one LED is active at a time — the first technology to detect (PIR or MW) lights first, followed by the red Alarm LED.
The detector ships with a standard swivel for flexible mounting angle. Key steps: open the front cover and release the internal base; open the W1/S1/S2/S3 knockouts on the external base; relocate the back tamper to the swivel's S5 position; mount via direct wall mounting or with the optional Conduit Metal Swivel Adaptor (CSMA, P/N RA300SC0000A, sold separately) for conduit-routed wiring in 16mm or 21mm diameters; connect the external base to the swivel using the dedicated snaps and securing screws; tilt/rotate to the desired angle and lock the angle-locking screw (each click = 5° of vertical/horizontal adjustment); reassemble and walk-test.
Lens types included: Wide Angle (RL300, 15m/50ft @ 90°), Low-Installation Pet Lens (RL300F, for mounts below 1.7m/5'6"), Long-Range Lens (RL300LR, up to ~23m/75ft), and Barrier Lens (RL300B, narrow 5° coverage). Each unit ships with the standard swivel plus all three replacement lenses (pet, long-range, barrier) in addition to the installed wide-angle lens.
| Current consumption (Relay Mode) | 45mA standby, 70mA max with LED on, at 12VDC |
| Current consumption (BUS Mode) | 30mA standby, 55mA max with LED on, at 12VDC |
| Voltage requirements | 9–16 VDC |
| Alarm / AM contacts | 24VDC, 0.1A |
| Dust output | Open collector, 70mA max |
| Size (L x W x D) | 220 x 115 x 123mm (8.7 x 4.5 x 4.85 in.) |
| Weight | 0.632 kg (1.4 lb) |
| RF immunity | 30MHz–2GHz: 40V/m |
| Operating/storage temperature | -30°C to 60°C (-22°F to 140°F) |
| Part Number | Description |
|---|---|
| RK315DT0000A | WatchOUT DT 10.525GHz + Swivel |
| RK315DT00UKA | WatchOUT DT 10.587GHz + Swivel |
| RK315DT00FRA | WatchOUT DT 9.9GHz + Swivel |
| RA300B00000A | WatchOUT Barrier Swivel Kit |
| RA300P00000A | WatchOUT Pole Adaptor Kit |
| RA300C00000A | WatchOUT Conduit Adaptor Kit |
| RA300SC0000A | WatchOUT Swivel Metal Conduit Adaptor |
| RA300VC0001A | WatchOUT Camera Cover Adaptor |
Up to 32 BUS detectors can be installed on a single ProSYS RS485 BUS, saving cabling and enabling remote control/diagnostics. For maximum stability, keep total BUS wiring under 300m (1000 ft).
| +, - | 12VDC power — connect (+) to ProSYS AUX RED and (-) to COM BLK |
| Yellow | Data communication — connect to ProSYS BUS YEL |
| Green | Data communication — connect to ProSYS BUS GRN |
| Tamper, LED, Enable | Used for tamper detection wiring configuration (cover tamper only, cover + back tamper, or cover tamper wired to a zone input) |
Set a unique ID (01–32) per detector using DIP switches 1–5, following the same binary-style pattern used for other ProSYS BUS accessories. DIP switches 6–8 are unused in BUS mode.
From the User Menu: Maintenance → Diagnostic → BUS Zone (Quick Keys [4][9][1]), enter the zone number to test. The system reports: detector input voltage, PIR channel 1/2 DC level (0.1–4V) and AC noise level (0–4VAC), and MW channel 1/2 DC level (0.1–4V) and AC noise level (0–4VAC) — useful for verifying detector health remotely.
Compatible with ProSYS software v4.xx+ and programmable via UD Software v1.8+.