0

Your Cart is Empty

  • Add description, images, menus and links to your mega menu

  • A column with no settings can be used as a spacer

  • Link to your collections, sales and even external links

  • Add up to five columns

  • Leviton Lumina RF 0-10V Dimming Wall Switch (ZSD07-ADZ) — Installation & Quick Start Sheet

    September 08, 2026 7 min read

    Installation and Quick Start Sheet for the Leviton Lumina RF 0-10V Dimming Wall Switch, Cat. No. ZSD07-ADZ — 2.4GHz wireless dimming for 0-10V LED/fluorescent loads.

    Full text manual (for reference)

    Installation and Quick Start Sheet for the Leviton Lumina™ RF 0-10V Dimming Wall Switch, Cat. No. ZSD07-ADZ — a 2.4GHz wireless dimming switch for 0-10V LED/fluorescent ballasts, with a robust mechanical latching relay and multi-location control via a Lumina gateway.

    Warnings and Cautions

    • To avoid fire, shock, or death: turn off power at the circuit breaker or fuse and test that power is off before wiring!
    • Install and use in accordance with appropriate electrical codes and regulations; consult an electrician if unsure about any part of these instructions.
    • Use with copper or copper-clad wire only. For indoor applications only. Save these instructions.
    • Features a 10A robust/commercial mechanical latching relay for handling high inrush (LED) and large loads.

    Overview

    Lumina RF components communicate with each other via 2.4GHz radio frequency to provide remote lighting control. Line-powered devices act as routers, re-transmitting the RF signal from one device to another until the intended device is reached — routing the signal around obstacles and radio dead spots. A Lumina gateway is required for programming and control communication between devices.

    Switch Layout

    • Paddle top — ON. Paddle bottom — OFF.
    • Rocker up — tap to raise 3%, push and hold to raise continuously until released.
    • Rocker down — tap to lower 3%, push and hold to lower continuously until released.
    • Bright LED indicator — shows the current dimming level ("inconspicuous LEDs").
    • Locator LED — lit when the switch is off, to help you find the control in the dark.

    Changing the Switch Color

    Supplied with white, ivory, and light almond switch plates (additional colors available from your Leviton distributor). Before wiring/installation: push in at the two tabs on the side to release the plate, then line up and press the new plate's side in to attach.

    Wiring

    The switch wires directly to the load and uses a mechanical latching relay for power switching from the Decora® rocker. It uses 0-10V (Violet and Gray) wires to connect to the fixture for dimming. When multiple switches control the same load, wire each switch identically per below — multi-location control is completed through programming via the Lumina gateway (required for all installations).

    Wiring Connections

    • Load (Blue) wire connects to the lighting load.
    • Neutral (White) wire connects to the neutral supply.
    • Line (Black) wire connects to a single phase of the 120-277V supply.
    • Violet wire connects to the +0-10V line; Gray wire connects to the common 0-10V line.

    The 0-10V control lines connect through a sleeve/connector arrangement to the 0-10V ballast/LED driver's Violet and Gray leads.

    Installation

    1. Turn off power at the circuit breaker or fuse and test that power is off before wiring.
    2. If replacing an existing switch, remove the faceplate, remove the switch from the wall box, and disconnect its wires. Identify the "Line," "Neutral," "Load," and "Traveler" (if present) wires. Note: an existing traveler wire is not needed for multi-location control with this switch — cap and tape it so it can be safely abandoned.
    3. Remove 3/4" of insulation from each wire on the switch and connect per the wiring diagram above.
    4. Confirm all wire connectors are firmly attached with no exposed copper.
    5. Place the wires and switch into the wall box with the LED at the bottom of the device, and attach using the supplied screws.
    6. Before installing the faceplate, restore power and verify the locator LED lights and ON/OFF operation works.
    7. After testing all switches for proper local operation, install a Decora faceplate over each switch.

    Class 2 Installation Note

    This switch can be installed as Class 1 or Class 2. If installed as Class 2 (per NEC Code NFPA 70, paragraph 725.136(d)), all devices in the circuit must be Class 2 rated, and the 0-10V control wires must be mechanically separated from Class 1 line/neutral/ground power lines by one of the following methods:

    1. Install a mechanical barrier (silicone tubing or other non-conducting sleeve) over the full length of the 0-10V (Violet & Gray) control wires inside the electrical box.
    2. Use approved, listed wire connectors to join the 0-10V control wires to the building's control wires.
    3. When used with a 120V~ source and CL3/CL3R/CL3P-rated control cables (or a permitted substitute) between building devices, the sleeve isn't required over control wires between the connector and the electrical box exterior — but a sleeve is still required over the control wires exiting the dimmer switch and entering the wire connector.

    Silicone tubing must be NRTL (UL/CSA/ETL) recognized or equivalent, providing mechanical separation equal to .25" in air. Connectors joining 0-10V control wires must be approved, listed connectors. Wire connectors and tubing are supplied by the installation contractor.

    Switch Operation

    Local Rocker Switch

    The rocker controls the load directly (paddle for on/off, rocker for dimming).

    LED Indicators

    The locator LED is normally lit green when the load is OFF, and off when the load is ON. A separate dimming indicator on the left side shows the current dimming level via a single bright LED, with the remaining LEDs lit dimmer to show the overall range — the bright LED moves up/down as you press the Dim/Bright rocker.

    Setup Mode for Controls Communication

    Configure the switch using a Lumina gateway — visit cloud.leviton.com for gateway installation software. The device must be in Mode 1 (Enrollment) while the gateway is searching for new devices.

    Operation Modes

    Mode / Blinks Operation
    1 Enrollment — allows the device to enroll in a network, or be removed.
    2 Identify — the device enters identify mode.
    3 RF Pairing — searches for compatible devices already in Identify Mode.
    4 LED Operation — enable/disable locator LED.
    5 Reset — resets the device to factory default settings.

    To enter the configuration menu at any point: press and hold the bottom (OFF) rocker for >10 seconds until the LED switches to amber blinking (Mode 1). From there, tap the bottom rocker to cycle through modes 1-5 (each tap advances one mode/one additional blink), then press and hold the bottom rocker for >5 seconds to execute that mode's action. Tap the top (ON) rocker to exit at any point. The menu times out after 20 seconds of no button presses.

    Mode 1 — Enroll / Remove from RF Network

    To add: in Mode 1, review the Lumina gateway instructions and power it up first; then press and hold the bottom rocker >5 seconds to enroll (green blinking until complete or timeout). To remove: in Mode 1, press and hold the top rocker >5 seconds to leave the network (red blinking until complete).

    Mode 2 — Identify

    Press and hold the bottom rocker >5 seconds to enter a 60-second RF Identify Devices window (green blinking until timeout or button press).

    Mode 3 — Pairing

    Press and hold the bottom rocker >5 seconds to search for compatible devices currently in Identify Mode (amber on entry, then 3 seconds solid green for success or solid red for failure). Press and hold the top rocker >5 seconds to clear the paired device list. Note: pairing happens quickly once it finds a device in Identify mode; both devices need to be enrolled in the network first, and both need Pairing + Identify performed for full 3-way control. Maximum of 8 paired devices.

    Mode 4 — LED Operation

    Press and hold the bottom rocker >5 seconds to toggle the locator LED mode — green confirmation blink means the LED will operate normally; red confirmation blink means the locator LED will be disabled and stay off.

    Mode 5 — Reset

    Press and hold the bottom rocker >5 seconds to enter Factory Default pending mode (red blinking until the top rocker is pressed to initiate). Then press and hold the top rocker >5 seconds to complete the reset (stops red blinking, returns to normal operation).

    Specifications (ZSD07-ADZ)

    Input voltage 120-277 VAC, 50/60 Hz
    LED/CFL load rating 120V: 8A, 960VA · 277V: 5A, 1385VA
    Incandescent/Tungsten load rating 120V: 800W
    Electronic ballast / inductive load rating 120V: 8A, 960VA · 277V: 5A, 1385VA
    Ballast load rating 120V: 10A, 1200VA · 277V: 10A, 2700VA
    Motor load rating 120V: 1/4 Hp · 277V: 1/3 Hp
    LED loads / Motor operated appliances Yes / Yes
    Connections 16 AWG (power), 18 AWG (0-10V)
    Dimensions 4.13" x 2.12" x 1.43" (104.9 x 53.95 x 36.42 mm)
    Weight 0.25 lbs, 0.11 kg
    Mounting Standard switch boxes, multi-gang allowed; uses standard Decora face plates
    Frequency / Range 2.4 GHz / 75-150 ft.
    Maximum load (0-10V control) 50 mA sinking
    Power consumption 120VAC @ 9.2 mA AC (530 mW typical) · 277VAC @ 5.7 mA AC (810 mW typical)
    Operating temperature 0°C - 40°C (32°F - 104°F)
    ETL certification UL-508, CAN/CSA-C22.2 No. 14

    FCC / Industry Canada Compliance

    Contains FCC ID: W7Z-ZICM357SP0. Complies with Part 15 of the FCC Rules (Class B digital device) — designed to provide reasonable protection against harmful interference in a residential installation, though interference is not guaranteed not to occur. If interference to radio/TV reception occurs, try reorienting the receiving antenna, increasing separation between the equipment and receiver, connecting to a different circuit, or consulting a technician. Changes or modifications not expressly approved by Leviton could void the user's authority to operate this equipment.

    Contains IC: 8254A-ZICM357SP0. Complies with Industry Canada license-exempt RSS standard(s); this Class B digital apparatus complies with Canadian ICES-003.

    Warranty

    Leviton warrants to the original consumer purchaser that Lumina-branded products will be free from defects in material and workmanship for two (2) years from installation or 30 months from manufacture date, whichever is shorter (rechargeable batteries: 90 days; primary batteries not warranted). Leviton's obligation is limited to repair or replacement, at its option, of product that fails due to a material/workmanship defect. Leviton is not responsible for labor costs of removal or reinstallation, and repaired/replaced products carry the remainder of the original warranty period or 90 days, whichever is longer. This warranty does not cover PC-based software products, and Leviton isn't responsible for issues from improper installation, normal wear and tear, catastrophe, or user negligence. Full warranty details and return instructions at www.leviton.com.

    For Canada: contact Leviton Manufacturing of Canada Ltd, Attn: Quality Assurance Department, 165 Hymus Blvd, Pointe-Claire (Québec), Canada H9R 1E9, or 1-800-405-5320.

    Technical Assistance: 1-800-824-3005 (U.S.A. only) · www.leviton.com

    © 2016 Leviton Mfg. Co., Inc.