September 08, 2026 5 min read
Installation and operation instructions for the Leviton Designer Wall Switch Occupancy Sensor (Cat. No. ODS10-IDx), covering wiring, blinders, time-delay, and ambient light settings.
Installation and operation instructions for the Leviton Designer Wall Switch Occupancy Sensor (Cat. No. ODS10-IDx), a single-pole or multi-location motion sensor that automatically switches lights ON and OFF based on detected occupancy.
The ODS10-IDx detects motion from a heat-emitting source (such as a person entering a room) within its field-of-view and automatically switches lights ON and OFF. Controlled lights remain ON until no motion is detected and the scheduled time-delay has expired. The sensor is UL listed, CSA certified, and conforms to California Title 24 requirements.
The sensor covers up to 2,400 sq. ft. (223.3 m²) using a small semiconductor heat detector behind a multi-zone optical Fresnel lens, which establishes dozens of detection zones. It is most effective sensing motion across its field-of-view, and less effective sensing motion moving directly toward or away from it.
Occupancy sensors respond to rapid temperature changes, so avoid mounting near climate-control sources (radiators, air exchanges, air conditioners) — hot or cold drafts can look like body motion and trigger false activation. Mount at least 6 ft. away from climate-control sources and from large-wattage bulbs (over 100W incandescent), which also emit heat that can trigger the sensor. Do not mount the sensor directly under a large light source. The device fits a single-gang wallbox.
WARNING: To be installed and/or used in accordance with appropriate electrical codes and regulations. If unsure about any part of these instructions, consult a qualified electrician. Controlling a load in excess of specified ratings will damage the unit and pose risk of fire, electric shock, personal injury, or death. Do not install this unit to control a receptacle.
Wiring notes: Use copper or copper-clad wire only; with aluminum wire, use devices marked CO/ALR or CU/AL only. Do not touch the lens surface — clean the outer surface with a damp cloth only. Disconnect power when servicing the fixture or changing bulbs.
Two independently-operating blinders narrow the field-of-view to prevent unwanted activation from traffic in adjacent spaces. Move the blinder adjustment levers (above the control knobs, below "BLINDERS") toward or away from the center using a finger or small screwdriver. With both levers fully toward center, field-of-view narrows to 32°; fully away from center, field-of-view is a maximum 180°.
Selects how long lights stay on after motion stops ("time-out"), chosen from four preset values via the face marking arrow:
| Face Marking | Value of Time |
|---|---|
| Slash Mark (/) | 30-second fixed time-out (used for walk-testing) |
| 1 | 10-minute time-out |
| 2 | 20-minute time-out |
| 3 | 30-minute time-out |
Factory preset is 10 minutes. All durations are approximate within 10 seconds.
Keeps lights from turning ON if there's already enough natural/artificial light in the room. To set:
Manual ON Mode: With Light Control fully CCW, lights never turn on automatically — they must be manually turned ON via the push-button and will turn OFF with absence of motion. Fully CW, lights turn ON with any detected motion, even in full daylight.
Rotate the range knob CCW to decrease detection range/sensitivity, adjustable from 100% down to 36%.
Push-Button: Toggles the lights. If OFF, pressing turns lights ON (remaining ON with motion present); if ON, pressing turns lights OFF (staying OFF regardless of motion until time-out expires — useful for presentations). The Motion Indicator LED blinks every 2 seconds while motion is detected.
| Symptom | Fix |
|---|---|
| No response 1½ minutes after power applied (light never turns on, LED never blinks) | Uninstall device and verify ground connection at the wallbox; check wiring. |
| Lights never turn ON but LED blinks | Check whether the Ambient Light Control Knob is fully CCW; rotate CW until lights turn ON. |
| Lights constantly stay ON even when unoccupied | Check the Time setting; lower the Range Control ~30° CCW; use Blinders to block hallway traffic; check for reflected heat through a window; check for adjacent HVAC/heater ducts. |
For additional information, call Leviton's Technical Support Line: 1-800-824-3005 (U.S.A.) or 1-800-405-5320 (Canada).
Single Control Application: Hot (Black) and Neutral (White) connect to Line; Black lead of sensor connects to Load; Blue lead connects to Load side; Green lead connects to Ground.
Two-Location Control Application: Two sensors wired in parallel — either sensor can turn the lights ON; either sensor must time out to OFF, or both manual push-buttons must be pressed, for the lights to turn OFF.
Leviton warrants this product free of defects in materials and workmanship for five years from the purchase date, limited to repair or replacement at Leviton's option. Warranty excludes labor for removal/reinstallation and is void if the product is installed improperly, overloaded, misused, opened, abused, or altered. Contact Leviton Manufacturing Co., Inc., Quality Assurance Dept., 59-25 Little Neck Parkway, Little Neck, NY 11362-2591.