Installation manual for the HAI Model 83A00 Power Hub — a 12VDC power supply with battery backup for HAI Access Control Card Readers, Omni Consoles, and OmniTouch Touchscreens.
Installation manual for the HAI Model 83A00 Power Hub — a general-purpose 12VDC power supply with battery backup, designed to power HAI Access Control Card Readers, Omni Consoles, OmniTouch 5.7 Touchscreens, and other HAI equipment. Available in the OmniLT Series Enclosure (83A00-1) or on a Universal Mounting Plate for Structured Wiring enclosures (83A00-2).
Each Power Hub MUST be grounded to the controller. The HAI controller and Power Hub(s) must be grounded together to prevent current flowing through the RS-485 data bus (connections A and B). Improper grounding can damage the controller, Power Hub, Access Control Card Readers, Omni Consoles, and/or OmniTouch Touchscreens. Connect the "GND" terminal on the Power Hub (under "CONTROLLER") to a "GND" terminal on the HAI controller.
Any 12VDC devices (up to 5 Amps total) connect to the "12V" and "GND" terminals under "DEVICE 1 – DEVICE 8".
Devices connected to "DEVICE 1–4" and "DEVICE 5–8" can share a communications path or be separated, controlled by switch "SW1":
The 75A00-1 requires 4 wires (2 power, 2 communications): connect Red, Black, Gray, and Orange wires to the 12V, GND, A, and B terminals respectively. Only use DEVICE 1–4 terminals unless SW1 is in "CONNECT" position.
Maximum cable length depends on wire gauge and current draw of the connected door lock. As a reference (24-gauge solid, single positive/ground conductor):
Heavier gauge wire (down to 16 AWG) or multiple conductors ganged together (e.g. from Cat-5 cable) significantly extends these distances — see the full spec table in the downloadable PDF for all combinations.
Connect the supplied 4-conductor modular cable between a Power Hub modular connector (J301 or J302) and a serial port (J1–J5) on the HAI controller. The serial port used for access control must be configured for RS-485 (set the corresponding interface jumper JP1–JP5 to the "485" position).
Warning: Do not connect J301/J302 to a controller serial port if SW1 is in "CONNECT" position AND the Power Hub's controller A/B terminals are also connected to the controller's console A/B terminals.
When more than 8 readers are needed, or extra power/distance is required, chain multiple Power Hubs: connect "J302" on the first hub to "J301" on the second, "J302" of the second to "J301" of the third, and so on. Connect "J302" of the last hub to a serial port on the HAI controller.
Requires 4 wires (2 power, 2 communications): connect Red, Black, Yellow, and Green wires to the 12V, GND, A, and B terminals respectively. Only use DEVICE 5–8 terminals unless SW1 is in "CONNECT" position.
Maximum cable length (reference, 24-gauge solid): 113 ft, scaling up to 724 ft with 16-gauge solid wire. The combined distance between Power Hub↔controller and Power Hub↔touchscreen must never exceed 1000 feet total.
Note for OmniLT controllers: the Power Hub's "A" terminal connects to the OmniLT's "YEL" terminal, and "B" connects to "GRN" under the "CONSOLE" section.
Connect the "LB+" and "LB-" terminals (under "CONTROLLER") to an available zone's "+" and "-" terminals on the HAI controller. Do not use an end-of-line resistor (the touchscreen has a built-in 1K ohm resistor). Configure the zone as "Trouble." When batteries drop below the voltage threshold, LB+ and LB- open, tripping the zone.
| Operating range | 32–120°F (0–49°C), 10–85% RH non-condensing |
| Power Pack output | 19VDC, 4.74A, max 90W |
| Power Pack input | 100–240VAC, 1.5A, 50/60Hz |
| Output power | Nominal 12VDC, max current 5A |
| Batteries | Sealed, rechargeable, 12V, 4–8 amp-hours each (not included) |
| Low voltage cutout | 9.5VDC |
| Main fuse | 4A polyfuse (permanent, no replacement needed) |
| Battery fuses | 6A polyfuse (permanent, no replacement needed) |