Installation instructions and wiring diagrams for the HAI Model 75A00-2 proximity card Access Control Reader for HAI Home Control Systems.
Installation instructions for the HAI Model 75A00-2 Access Control Reader — a 125 KHz high security, digitally encrypted, 26-bit proximity card reader that connects to a serial port on an HAI Home Control System for access control.
Multiple 75A00-2 readers may be multi-dropped on a single serial interface configured for RS-485 communications. The reader incorporates three inputs — one for an exit push button and two general purpose inputs — plus one output for an electric door strike or magnetic lock.
The 75A00-2 requires 4 wires for operation (2 for power, 2 for communications). Maximum cable distance between the reader and the connected 12V Power Supply (or HAI 83A00 Power Hub) depends on the current draw of the connected door lock device and the wire gauge/type used. Do not exceed these maximum cable lengths:
| Wire Gauge / Type | 75A00-2 Only (130mA max) | + 79A00-1 Strike (580mA max) | + Door Lock 800mA (930mA max) | + Door Lock 1A (1.13A max) |
|---|---|---|---|---|
| 24 AWG solid, 1 conductor pair | 233 ft | 58 ft | 37 ft | 30 ft |
| 24 AWG solid, 2 conductor pairs | 466 ft | 117 ft | 74 ft | 61 ft |
| 22 AWG solid, 1 conductor pair | 413 ft | 103 ft | 65 ft | 54 ft |
| 18 AWG solid, 1 conductor pair | 1000 ft | 261 ft | 165 ft | 136 ft |
| 16 AWG solid, 1 conductor pair | 1000 ft | 415 ft | 262 ft | 217 ft |
Note: If cable with multiple conductors is used (such as Cat-5), multiple conductors can be connected together to achieve greater distance.
The 75A00-2 connects via a 4-position modular connector (gray wire on top, tab up):
| Wire Color | Connection |
|---|---|
| Red | Power (+12VDC) |
| Black | Power Ground (GND) |
| Gray | RS-485 (A) |
| Orange | RS-485 (B) |
| White | Door Lock Output |
| Green | Exit Button Input |
| Blue | Contact Input #1 |
| Yellow | Contact Input #2 |
| Purple / Brown | Not Used |
Additional readers connect in parallel on the 4-position modular connector. When a serial interface is configured for access control, the corresponding interface jumper (JP1–JP5) must be in the "485" position — for example, JP2 must be set to "485" when serial interface 2 (J2) is used for access control.
The reader can be wired directly to a 12VDC power supply (with 24VAC transformer input) or to an HAI Model 83A00 12VDC Power Hub connected to the HAI controller — both configurations use the same wire-color connections listed above.
| Read Range | 78A00-1 Cards = 4 in.; 78A00-2 Key Tags = 2 in. |
| Door Open Time | 5 seconds default, 1–60 seconds selectable |
| Current Consumption | 130mA maximum |
| Communications | RS-485 |
| Inputs | 3 (Exit Button, Input 1, Input 2) |
| Lock Output | 12VDC, 1A maximum |
| Lock Type | Fail Safe or Fail Secure (selectable) |
| LED Indicators | Array of 3 (Red and Green) |
| Beeper | Piezoelectric |
| Operating Temperature | -31°F to 140°F |
| Operating Humidity | 10% to 90% relative humidity, non-condensing |
| Dimensions | 1.8"W x 4.9"H x 0.8"D |
| Weight | 80g (0.18 lb.) |
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) it must accept any interference received, including interference that may cause undesired operation. Tested and found to comply with Class A Digital Device limits under Part 15.