Complete hardware installation guide for the GE Security TOPAZ ACURT2 and ACURT4 networked intelligent access control controllers.
Hardware Installation Guide for the GE Security TOPAZ ACURT2 and ACURT4 Networked Intelligent Controllers — access control field panels supporting 2 or 4 card readers, RS-485/RS-232/Ethernet host communication, and expansion modules for additional alarm inputs and relay outputs.
The ACURT2 and ACURT4 are networked intelligent access control panels. The ACURT2 supports 2 card readers; the ACURT4 supports 4 card readers. Both support a Host Port (RS-232 or RS-485), an Ethernet Port, and an Expansion Module Port for connecting up to 4 RIM (Remote Input Module) and/or RRM (Remote Relay Module) expansion boards.
| Characteristic | Specification |
|---|---|
| Height | 16.25 in (41.28 cm) |
| Width | 16.375 in (41.59 cm) |
| Depth | 4.125 in (10.48 cm) |
| Weight (with batteries) | 19 lb (8.6 kg) |
| Weight (without batteries) | 16 lb (7.3 kg) |
| Max Temperature | +150°F (+65°C) |
| Min Temperature | +32°F (0°C) |
| Humidity | 0-95% relative (non-condensing) |
| Input Power | 24 VAC, 40 VA |
| DC Standby Battery Backup | 4-hour backup |
| DC Input Rating | +24VDC ±4V @ 750mA max (all outputs at max load) |
RS-485 is a differential-voltage communication circuit with 120-ohm impedance. End-of-line terminators are required at both ends of the communications path. Multi-drop configurations are allowed up to 4000 feet; stubs off the main cable must not exceed 10 feet and must not be terminated. Star configurations should be avoided.
The ACURT2/ACURT4 controllers have switch-selectable RS-485 termination on each host and expansion module port. An RS-485 terminator is required at the NCIC-5 converter. Remote Modules (RIM/RRM) have no built-in terminator — the farthest unit from the ACURT needs an external terminator (part #124-824).
Each ACU panel on the communication loop must be individually connected to earth ground — not chassis or electrical ground. Proper grounding is essential for reliable data communication and for the panel's built-in transient voltage protection to function. Cold water pipes or a grounding rod typically make a good earth ground.
Switches SW1–SW7 configure communication termination, baud rate, addressing, and zone termination. Note: SW2, SW3, and SW4 are read only at power-up and ignored thereafter — power must be cycled after changing any switch settings (SW7 can be used to cycle power).
| Switch | Function (ON) |
|---|---|
| S1 | Host TX Line Terminated |
| S2 | Host RX Line Terminated |
| S3 | Expansion Module Port TX Line Terminated |
| S4 | Expansion Module Port RX Line Terminated |
| S1 | S2 | S3 | Baud Rate |
|---|---|---|---|
| OFF | OFF | OFF | 19200 |
| ON | OFF | OFF | 38400 |
| OFF | ON | OFF | 57600 |
| ON | ON | OFF | 1200 |
| OFF | OFF | ON | 115200 |
| ON | OFF | ON | 2400 |
| OFF | ON | ON | 4800 |
| ON* | ON* | ON* | 9600 (default) |
S4: DES Encryption Enabled (OFF = default). S5: ON = Dial-Up Host Comm, OFF = Dedicated (default). S6: ON = 5-wire RS-232 (RTS/CTS), OFF = RS-485 or 3-wire RS-232 (default). S7: spare, set OFF. S8: ON = No Parity (modem), OFF = Even Parity (default).
S1: LAN Enabled. S2: Allow LAN IP Parameter Update. S3: Default LAN IP Parameter. S4: Triple DES Encryption Enabled. S5: Spare — leave OFF. S6: Magnetic Stripe Cards. S7: Battery Backed Up RAM (default ON). S8: Disable Watch Dog Timer.
Sixteen positions (0–F hexadecimal) set the ACURT field panel address, 0 through 15.
ON = terminated (no input device present); OFF = not terminated (zone in use with an end-of-line resistor). SW5 covers Reader 0 (S1-S3) and Reader 1 (S4-S6) zones; SW6 covers Reader 2 (S1-S3) and Reader 3 (S4-S6) zones (ACURT4 only). If an exit push button isn't connected on zone 1, an additional 1000-ohm resistor must be installed across that zone input.
Slide switch that turns on the board's power supply — also used to cycle power after changing other DIP switches.
Power-Up Self-Test (LEDs 1-4 light in sequence): LED 1 = power-up, LED 2 = successful RAM test, LED 3 = successful PROM test, LED 4 = initialization complete (1 second). At power-up all LEDs turn ON; at hardware reset, all OFF.
Normal Operation: LED 1 flashes at 1 Hz. LED 2 is ON while transmitting to Remote Modules. LED 3 blinks once if Reader 0 is online, twice if Reader 1 is online, etc. (2 seconds OFF between cycles). LED 4 is ON if zone voltage reference is ever out of range (indicates board or power supply failure).
LAN LEDs: TX (transmitting), RX (receiving), COL (collision), Link (cable connected), Rev (cable reversed).
The ACURT2/ACURT4 use numbered terminal blocks for all field wiring: TB1 (Host Communication Port), TB2/3/4 (Reader 0), TB5/6/7 (Reader 1), TB8 (Expansion Module Communication Port RS-485), TB9 (Reader 0/1 Auxiliary Relay), TB10 (Power), TB11 (Cabinet Tamper), and on the ACURT4 only, TB12/13/14 (Reader 2), TB15/16/17 (Reader 3), and TB18 (Reader 2/3 Auxiliary Relay).
Supported readers wire directly to the ACURT2/ACURT4 with point-to-point wiring diagrams provided in the full manual for: HID ProxPoint Plus 6005, HID MiniProx 5365, HID ProxPro 5355, HID MaxiProx 5375 (long range, with jumper pin configuration), and the GE Security K11L keypad (with jumper configuration for reader support).
The optional RIM (Remote Input Module) adds alarm zone inputs 1-19 across terminal blocks TB1-TB10, with its own DIP switches and status LEDs, plus a field wiring test and power-up self-test procedure.
The optional RRM (Remote Relay Module) adds relay outputs 1-16 with its own DIP switches, field wiring test, and power-up self-test. An Elevator Control Relay Interface section covers elevator relay numbering and standard elevator wiring for access-controlled elevator floor selection.
The IP address can be set through the Ethernet port or through a serial connection — the manual details both procedures for the ACURT2/ACURT4's onboard network module.
Manufacturer: GE Security (TOPAZ product line). Manual number AV-136192, Revision G.7, June 21, 2004. GE Security, 12345 SW Leveton Drive, Tualatin, OR 97062. Support: 800-547-2556.