Installation and startup manual for the GE Security NetworX NX-507E Seven Relay Expander and NX-508E Eight Output Expander auxiliary modules.
Installation and Startup manual for the GE Security NetworX™ NX-507E Seven Relay Expander and NX-508E Eight Output Expander — auxiliary modules that expand the capabilities of NetworX security control panels for access control, home automation, wireless interfaces, and security functions.
For UL Commercial Fire systems, 18 AWG wire must be used, and the NX-507E must be mounted inside the control panel's own enclosure. Maximum wire run varies by wire gauge and by whether the module is connected directly to the NetworX control panel or to an NX-320E supply, and whether the AUX terminal is used:
| Wire Run | NX-507E (all relays active) / NX-508E — to NX panel | NX-507E (no relays active) — Using AUX | To NX-320E — Using AUX |
|---|---|---|---|
| 250 ft | 20 AWG | 24 AWG | 22 AWG |
| 500 ft | 16 AWG | 20 AWG | 18 AWG |
| 1000 ft | 14 AWG | 18 AWG | 16 AWG |
| 1500 ft | 12 AWG | 16 AWG | 14 AWG |
| 2500 ft | 10 AWG | 14 AWG | 12 AWG |
Set the module's bus address using the onboard DIP switches (addresses 24–31), per the address table in the manual. DIP switch 4 disables the tamper feature (On = enabled, Off = disabled).
NetworX panels automatically find and store all keypads, zone expanders, wireless receivers, and output modules in memory once Program Mode is exited. The enrolling process takes about 12 seconds (Service LED illuminates; user codes are not accepted during enrollment). If an enrolled module later goes undetected, the Service LED illuminates to flag it.
Enter Program Mode ([Á]-[8], then the installer "Go To Program" code — default 9-7-1-3). Enter the module's address followed by [#], then the desired programming location followed by [#]. Binary/numerical data is entered per segment, followed by [Á] to advance; [#] exits the location. Programming data is either numerical (0–255 or 0–15 depending on segment size) or feature-selection (on/off per bit).
The module mounts using two PCB guides: position the first guide (grooved edge down) in the upper insertion point and screw it in; position the second guide (grooved edge up) in the lower insertion point and screw it in. The PC board should then slide freely in both guides' grooves.
| Parameter | Value |
|---|---|
| Dimensions | 1" W × 6" L × 3" D |
| Operating power | 12 VDC, supplied from NX control panel or NX-320E |
| Auxiliary power | Supplied by NX panel/NX-320E, limited to 100 mA by the expander |
| NX-507E current draw | 10 mA (no relays active) to 310 mA (all relays active), plus attached device draw |
| NX-508E current draw | 10 mA (no outputs active) to 25 mA (all outputs active), plus attached device draw |
| Operating temperature | 32°F to 120°F |
| Shipping weight | 1 lb. |
NX-4, NX-4V2, NX-6, NX-6V2, NX-8, NX-8V2, NX-8E, NX-8-CF, NX-8E-CF
Reference: NX507E-508EIH05 Rev H (May 2005). GE Security Technical Support: 888-437-3287.