  • GE Security ESL 505 — CleanMe Module Installation Instructions

    August 31, 2026 3 min read

    Installation instructions for the GE Security ESL 505 CleanMe Module, an interface between 500 Series two-wire smoke detectors and a UL Listed control panel.

    Full text manual (for reference)

    Installation instructions for the GE Security ESL 505 CleanMe® Module — an interface between a 500 Series two-wire smoke detector and a UL Listed control panel.

    Description

    The ESL 505 CleanMe® module interprets a 500 Series detector's trouble (CleanMe®) signal and outputs it to the control panel via relays, letting installers remotely receive maintenance alerts (e.g. detector needs cleaning) before a false alarm occurs. It also flags general detector trouble such as a hardware fault. The module can additionally convert two-wire smoke detectors to a four-wire panel input, useful when a panel lacks two-wire smoke detector loop inputs. Each module accommodates up to 20 smoke detectors.

    Diagnostic LEDs

    • Top yellow LED — Smoke Detector Trouble (CleanMe®): indicates one or more detectors on the loop are dirty or have a hardware fault. The affected detector blinks rapidly (every 1.5 seconds) — see the detector's own installation instructions. Output is via the module's form C trouble relay.
    • Middle yellow LED — Loop Fault Trouble: indicates a problem such as a broken wire that could prevent all or part of the loop from signaling an alarm during a fire. Resolve immediately; the LED resets automatically once the fault clears.
    • Bottom red LED — Power/Alarm: blinks every 9 seconds to indicate power to the loop; latches solid ON during a smoke detector alarm and resets when power drops. Alarm output is via the module's form A alarm relay.

    DIP Switches (on 500 Series detector back)

    Switch Description
    1 ON = 6–12V, OFF = 12–24V
    2 ON = Enables CleanMe®, OFF = Disables CleanMe®

    Important: Switch 2 on the back of the 500 Series detector must be ON to enable the CleanMe® signal.

    Wiring Configurations

    • CleanMe® signal to a separate zone: wire the module so the CleanMe® signal reports to a dedicated panel zone (labeled "smoke detector trouble"), letting an installer remotely distinguish a dirty-detector trouble signal from a general loop fault (e.g. cut wire). All detectors on the loop must use the same voltage range setting.
    • CleanMe® signal as general trouble: wire the module so the CleanMe® signal reports to the panel as a general fire trouble signal. In this configuration, the installer must diagnose on-site using the module's LEDs to determine dirty detector vs. general loop fault. All detectors must use the same voltage range setting.
    • 2-wire to 4-wire conversion: for older combination burglar/fire panels lacking a two-wire smoke detector loop input, the module converts 2-wire detectors to 4-wire panel inputs. All detectors on the loop must use the same voltage range setting.
    • Polarity reversal (two-to-four-wire converter mode): using an ESL 405-01 (24VDC) polarity reversal relay, two-wire sounder smoke detectors (429 series) can be wired so that when one detector alarms, all sound in alarm.

    Module terminals J1–J12 provide CleanMe® relay, Alarm relay, and Supervision relay connections along with detector loop in/out terminals, per the specific wiring diagram for your configuration (see the downloadable PDF for full wiring diagrams).

    Mounting

    • Mounts to a 4-inch square electrical box (not included), minimum depth 2 1/8".
    • Install module wiring per your chosen configuration before securing the module.
    • All wiring must conform to applicable local codes, ordinances, and regulations. The module is powered by the control panel's auxiliary power supply.

    Compatibility

    Compatibility ID Model Numbers
    S09A 429AT, 521B (sw on), 521BXT (sw on)
    S10A 429C, 429CT, 521B (sw off), 521BXT (sw off), 711U, 711UT, 721U, 721UT, 722U
    S11A 429CRT, 429CST, 429CSST, 521CRXT, 731U, 732U

    Product Specifications

    • Powered from panel's auxiliary power supply; Operating Voltage: 12–33V DC (if panel power drops below 12V, the module may not operate properly)
    • Typical Standby Current: <20mA; Alarm Current: 50mA ±10%
    • Form A contacts: 500mA@36V DC (resistive); Form C contacts: 2A@28V DC or 30V AC (resistive)
    • Maximum reset time: 3 sec; Line resistance (total): 30 ohms max
    • Number of detectors per module: 20
    • Operating Temperature: -4°F (-20°C) to 131°F (55°C); Humidity: 0–95% non-condensing
    • RFI immunity: 20V/M @ 0–1GHz; Static immunity: 25,000V; Transient immunity: 2500V @ 1.5J
    • Dimensions: Back box 2.75"H x 2.5"W x 1.25"D; Plate 5" x 5"; Weight: 5 lbs (232 gm)
    • Color: white/white; Mounts to 4" square, double gang boxes
    • Material: Flame retardant plastic cover (UL-94V-0)
    • Field wiring size: 12–24 AWG
    • Compatibility identifier: C02; Type: Class B; Listing: UL 864

    Ordering

    ESL505 — CleanMe® module