  • FortrezZ MIMOlite Wireless Interface/Bridge Module — Technical Appendix

    August 31, 2026 3 min read

    Technical appendix to the MIMOlite User Manual covering Z-Wave command classes, configuration parameters, self-test procedures, and analog input voltage conversion data.

    Full text manual (for reference)

    Overview

    This Technical Appendix supplements the FortrezZ MIMOlite Wireless Interface/Bridge Module User Manual with detailed Z-Wave protocol characteristics, Command Class configuration parameters, self-test procedures, and analog input voltage conversion data for advanced installers and integrators.

    Z-Wave Characteristics

    Manufacturer ID 0x0084
    Product Type ID 0x0453 (US) / 0x0451 (EU)
    Generic Device Class GENERIC_TYPE_SWITCH_BINARY

    Supported Command Classes

    • COMMAND_CLASS_MANUFACTURER_SPECIFIC
    • COMMAND_CLASS_VERSION
    • COMMAND_CLASS_ALARM (V1, for power fail)
    • COMMAND_CLASS_SENSOR_BINARY
    • COMMAND_CLASS_SENSOR_MULTILEVEL (analog ADC count on SIG1)
    • COMMAND_CLASS_METER_PULSE (triggering event count on SIG1)
    • COMMAND_CLASS_CONFIGURATION
    • COMMAND_CLASS_ASSOCIATION
    • COMMAND_CLASS_SWITCH_BINARY (controls/reports Relay1 status)

    Association Groups

    Group Behavior
    1 Input triggered/untriggered sends a Basic Set to turn associated device(s) on/off.
    2 Periodic MultiLevel Sensor report of the input's analog voltage level.
    3 Alarm Command Class report sent on power dropout (if residual power allows).
    4 Binary Sensor report sent when input is triggered/untriggered.
    5 Pulse meter counts sent periodically (same interval as Group 2).

    Maximum of two nodes per association group. Notes: MLS Association Groups 2 and 5 transmissions do not use explorer frames if nodes don't ACK; rapid triggers on Groups 1/4 can block transmissions to non-responding nodes; on power dropout, the MIMOlite likely only has enough residual power to notify the first node in Association Group 3.

    Configuration Command Class Parameters

    Parameter Function
    2 Clear Pulse Meter Counts (any value received resets the count)
    3 Trigger Mapping: SIG1 triggered/untriggered sets/clears Relay1 (default 0x00)
    4 Lower Threshold, High (default 0xBB)
    5 Lower Threshold, Low (default 0xAB)
    6 Upper Threshold, High (default 0xFF)
    7 Upper Threshold, Low (default 0xFE)
    8 Input Flags: Bit1 = Digital vs. Analog threshold mode; Bit0 = Trigger-Between-Thresholds flag
    9 Periodic report interval for SIG1 (10-second resolution, default 30s; 0 disables)
    11 Momentary Relay1 output enable/disable; value sets on-time in 100ms increments (default disabled)

    Self-Test Procedure

    Caution: Self-test overwrites all settings and removes the MIMOlite from the network.

    Entry: Hold the Program button while powering up the MIMOlite. The Status LED remains lit while held.

    1. EEPROM Test — writes/reads bytes from EEPROM. Success: SIG1 LED lights faintly. Failure: Status LED stays lit (test halts; erases prior Configuration Command Class setups).
    2. Software Verification Test — checksums program memory. Success: SIG1 LED turns off. Failure: Status LED stays lit (test halts).
    3. Relay Test — attempts to turn Relay1 on twice; relay clicks should be audible.
    4. RF Output Test — RF output for 2 seconds; SIG1 LED lights during this test (verify with spectrum analyzer).

    Tests run in sequence quickly; after Test 4 completes, the MIMOlite resets and resumes normal operation.

    Analog Input Voltage Conversion (SIG1)

    The input signal voltage converts non-linearly to a 12-bit Multilevel Sensor value (0–4095 counts), at a nominal 13.5V power supply. Do not exceed an input voltage of 16V. Selected reference points:

    Input Voltage ADC Counts (decimal)
    Open 2162
    Shorted / 0V 7
    1V 1179
    5V 2892
    10V 3286
    16V (max) 3523

    For triggering configuration, the lower 4 least-significant bits are dropped, producing an 8-bit trigger value (0–255 counts). Example: a ~2V trigger point (2057 decimal / 808 hex, 12-bit) corresponds to 80 hex / 128 decimal at 8-bit trigger resolution. It is recommended to verify configured trigger points using the Multilevel Sensor Command Class.

    The default analog trigger threshold for SIG1 is approximately 1V (matching the default digital threshold configuration). Triggering ranges can be configured to trigger between or outside two thresholds, with hysteresis at each endpoint to prevent chatter from small voltage fluctuations, via Configuration Command Class Parameters 4–8.

    Input-to-Relay Mapping

    The MIMOlite can be configured (Parameter 3, Bit 0) to automatically turn Relay1 on when input SIG1 is triggered. When enabled, Z-Wave commands to set the relay are overridden and no Z-Wave notification is sent on automatic relay changes — though relay state can still be queried via Basic Command Class Get or Binary Switch Command Class Get.

    Power Dropout Behavior

    A periodic Power Dropout status blink occurs if supply voltage drops below approximately 10.5V. The MIMOlite implements Alarm Command Class V1, sending an alarm report (Type 0x08, Level 0xFF) to Association Group 3 nodes on dropout, and a recovery report (Level 0x00) once power rises above approximately 11V.

    On power loss, the MIMOlite attempts to save pulse counts to non-volatile memory using residual circuit power, though this is not guaranteed — an external backup battery or periodic controller polling of pulse counts is recommended to avoid data loss.

    Manufacturer

    FortrezZ, LLC — 1080 Centre Rd. Ste C, Auburn Hills, MI 48326 · Phone: (248) 481-7092 · sales@fortrezz.com · www.fortrezz.com · Made in USA

    For warranty information, refer to the "Limited Warranty" section of the full MIMOlite User Manual.