September 08, 2026 4 min read
Installation and programming instructions for the ELK-M1ZTS/M1ZTSR zone temperature sensor and interface for the M1 or M1EZ8 control.
Installation and application instructions for the ELK-M1ZTS / ELK-M1ZTSR Zone Temperature Sensor / Interface — a temperature monitoring device for the ELK-M1 or M1EZ8 control panel, available with an internal built-in sensor (M1ZTS) or a remote 7' sensor probe (M1ZTSR).
This temperature interface, used with an ELK-M1 or M1EZ8 control, can monitor temperatures up to 1000 feet away, with results/actions programmed using ElkRP rules. The M1ZTSR (Remote 7' Sensor) is best for freezer monitoring or extreme conditions since it lets the interface be mounted indoors in a more suitable environment while the sensor probe reaches the monitored area.
| Spec | Value |
|---|---|
| Operating Voltage | 12 Volts D.C. |
| Current Draw | 10mA |
| Housing Dimensions | 3.5" x 2.5" x 0.875" |
Important: The M1ZTS is factory configured to read the internal built-in sensor; the M1ZTSR is factory configured to read the external sensor at the screw terminals. Elk does not recommend converting one model to the other — the internal and external sensors cannot be used simultaneously.
It takes ~30 seconds after power-up for the interface to stabilize and transmit a reading. Updates transmit every 17 seconds. The control discards rapidly changing readings — if a reading is more than 20 degrees higher or 9 degrees lower than the last reading, it's regarded as a possible error and discarded.
Example: turn on Output 3 for 10 minutes whenever the temperature exceeds 90 degrees.
Note: The control does not allow a temperature reading to be used directly as a trigger (to prevent false "runaway" activations from minor fluctuations) — instead, use the AND command to compare a temperature sensor reading against a target value each time another trigger occurs. Compare options are Equal to, Not equal to, Less than, and Greater than ("Equal to" isn't recommended since exact matches are unlikely).
Outside|% TEMP ZN15 %|
| Model | Description | UPC |
|---|---|---|
| ELK-M1ZTS v2 | Internal Built-in Sensor | 7 62158 55031 7 |
| ELK-M1ZTSR v2 | Remote 7 foot Sensor | 7 62158 55032 4 |
ELK Products, Inc. — PO Box 100, Hildebran, NC 28637 — 828-397-4200 — www.elkproducts.com