  • Broan-NuTone HRV70/ERV70 Series — User Guide

    August 31, 2026 4 min read

    User guide for the Broan-NuTone HRV70/ERV70 series Heat and Energy Recovery Ventilators — controls, defrosting, maintenance, and troubleshooting.

    Full text manual (for reference)

    Overview

    This user guide covers the Broan-NuTone Heat Recovery Ventilator (HRV) and Energy Recovery Ventilator (ERV) 70-series units: ERV70S/ERV70T (side/top ports) and HRV70SE*/HRV70TE* (side/top ports, ENERGY STAR® certified for Canadian use). These whole-house ventilation systems recover heat or energy from outgoing air to condition incoming fresh air, improving indoor comfort and efficiency.

    Register your product online at: www.broan.com/register

    ⚠ Important Cautions

    • Keep outside intake and exhaust hoods free of snow during winter — check the unit during heavy snowstorms so it doesn't draw in snow. If it does, run in recirculation mode or turn OFF for a few hours.
    • Do not use the unit during construction or renovation, or when sanding drywall — dust can damage the system.
    • The electronic control system uses a microprocessor and may misbehave due to external noise or a brief power failure. If this happens, unplug the unit, wait ~10 seconds, then plug it back in.

    Defrosting Mode

    When outside temperature drops below 23°F (-5°C), heat/energy recovery creates frost in the core. The unit automatically defrosts the recovery core, with defrost frequency varying by outside temperature. During a defrost cycle the unit shifts to maximum speed and the dampers close; afterward it returns to the previously selected operating mode.

    Controls

    Integrated Control

    Located on the upper-left side of the unit. Use the push button to control the unit; the LED shows the current mode.

    Press Push Button LED Color Result
    Once Amber Unit on LOW speed
    Twice Green Unit on HIGH speed
    Three times No light Unit OFF

    Booting sequence: each time the unit is plugged in after being unplugged or after a power failure, it runs a 30-second boot sequence. The LED lights GREEN for 5 seconds, then turns RED while the unit checks/resets the motorized damper position. No commands are accepted until boot completes.

    If a problem occurs, the integrated LED will blink; blink color indicates the error type (see Troubleshooting below).

    Note: when using an optional main wall control (VT4W), the integrated control must be turned OFF.

    Optional Main Control (VT4W)

    Only one VT4W can be connected to a unit. When power is first applied or after a power failure, the VT4W is in OFF mode by default; activate the push button to cycle modes.

    Light Color Mode Suggested Use
    Green Intermittent Away from home for a few days, or when indoor air is too dry (heating season) or too humid (cooling season). Unit runs OFF 40 min/hr, ventilates at minimum speed for 20 min/hr.
    Yellow Min Minimum ventilation speed for normal daily operation.
    Red Max Maximum ventilation speed for excess pollutants/humidity (parties, odors, smoke, etc.)
    No light Off Turn off before performing maintenance.

    Optional Auxiliary Controls (up to 5 can be connected)

    • 20-minute lighted push button: press once to activate 20 minutes of high-speed air exchange with the outside (indicator lights); press again to cancel early and return to the previous setting.
    • 60-minute crank timer: runs the unit at high speed for 10–60 minutes, adjustable via the dial.
    • Dehumidistat: adjust the knob to the desired maximum indoor humidity level. Caution: do not select a level below 30% — this can cause excessive dryness and occupant discomfort.

    Maintenance

    ⚠ Warning: risk of electric shock. Always turn off and unplug the unit before performing maintenance. Sharp edges may be present — wear safety glasses and gloves.

    Inner parts to know: (1) Heat or energy recovery core, (2) Core filters.

    Quarterly Maintenance

    1. Turn the unit OFF and unplug it.
    2. Remove the unit door: take out both door lower machine screws (No. 8-32 x 1"), open, and lift out the door.
    3. Slide out both filters and the recovery core.
    4. Clean the inside walls with a clean damp cloth, then wipe dry.
    5. Remove dust from filters and core with a vacuum and soft brush attachment.
    6. Wash both core filters under lukewarm water with mild soap, rinse thoroughly, and let dry completely before reinstalling.
    7. Follow the instructions on the core label to reinstall it correctly, then slide the core and cleaned filters back in.
    8. Reinstall the door with the previously removed screws and plug the unit back in. (The unit returns to its previous setting after the 30-second boot delay.)

    Annual Maintenance

    Perform the Quarterly Maintenance steps, plus clean the recovery core per the core label:

    • HRV units: soak the heat recovery core in lukewarm water with mild soap, rinse thoroughly, shake to remove excess water, and let dry.
    • ERV units: remove dust from the core with a vacuum and soft brush attachment.
    • All units: after reinstalling the core, filters, and door, clean the exterior hoods.

    Troubleshooting

    ⚠ Warning: never open the electronic box — no user-serviceable parts inside, including a fuse that should never be user-replaced. Refer servicing to qualified personnel.

    If the unit malfunctions, first try resetting by unplugging for one minute, then replugging.

    Problem Try This
    Unit does not work Check the unit is plugged in and receiving power from the house circuit breaker/fuse.
    Condensation on windows (air too humid) Review Controls section settings. Leave curtains half-open for air circulation. Store firewood in a dehumidified/ventilated room or outside. Don't set the heating thermostat below 64°F (18°C).
    Inside air too dry (cold season) Review Controls settings; temporarily use a humidifier.
    Air too cold at supply grille (cold season) Check exterior hoods (especially the exhaust) for blockage. Review Controls settings. Consider installing a duct heater.
    Integrated control LED blinking GREEN Thermistor problem — unit still works but will defrost frequently. Contact your installer.
    Integrated control LED blinking AMBER Motorized damper problem — unit is OFF and tries to reset the damper every 30 minutes for 2.5 hours before giving up. Contact your installer.
    Integrated defrost push-button doesn't work The 30-second boot sequence hasn't completed — see Integrated Control section.