  • Winland EnviroAlert EA800 — Multi-Zone Environmental Alarm System Manual

    September 08, 2026 5 min read

    Installation and owner's manual for the Winland EnviroAlert EA800 Multi-Zone Environmental Alarm System.

    Full text manual (for reference)

    Installation and owner's manual for the Winland EnviroAlert EA800 Multi-Zone Environmental Alarm System, which monitors up to 8 sensors (4 wired + 4 wireless) and provides alarm relay outputs when programmed limits are exceeded.

    Overview

    The EnviroAlert EA800 monitors environmental conditions from up to 4 wired and up to 4 wireless sensors (sold separately), and provides alarm signals when any sensor's readings exceed the user-programmable HIGH or LOW limit. Alarm signals are provided via dedicated relay outputs that can operate with process controls, security systems, or other automated equipment. Setup and programming is done via front panel keys and a graphic LCD display. Each sensor input has its own corresponding relay output, plus one AUX (Auxiliary) output that activates on any alarm condition, useful for connecting an audible alarm or strobe.

    Using appropriate accessory sensors, the EA800 monitors: temperature from –80°C to 150°C (–112°F to 302°F), humidity from 5% to 95% RH (non-condensing), presence of water, and any sensor with a 4-20mA interface. The console mounts directly to a standard 3-gang electrical enclosure or to walls; wireless sensors mount easily to a wall.

    Multiple EA800 units — or a mix of EA800, EA400, and EA200 systems — can be combined into a larger facility security/monitoring system, each feeding an alarm panel.

    Safety / Limitations of the Alarm System

    • No alarm system offers guaranteed protection against every failure — sensors can be bypassed, power can be interrupted, and telephone/wireless signal paths can be compromised.
    • Equipment is subject to component failure; weekly testing of detection devices, control panels, and keypads is recommended.
    • An alarm system is not a substitute for insurance.

    Sensor Types Supported

    • Temperature Sensors — wired thermistor probes (Red high-temp / Blue low-temp)
    • Humidity Sensors — 5% to 95% RH
    • 4-20mA Sensors — for process/industrial signals, with selectable power supply/sensor voltage
    • Water Sensors — presence-of-water detection
    • Multi-Function Sensors (EA-WMFS) — wireless combination sensor, up to 100 ft. (30 m) cable to remote probe
    • Dry Contact Sensors

    Installation

    Tools and Supplies Required

    Standard hand tools, wire strippers, and appropriate sensor/alarm wiring (18-22 AWG typical). Power source must furnish 11 to 26VDC @ 500mA, regulated and filtered, from an AC adapter (not included) or alarm panel.

    Mounting

    The EA800 console mounts directly to a standard 3-gang electrical enclosure using pre-drilled holes on the rear case, or can be mounted to drywall or similar surfaces using appropriate anchors (not included). Wireless sensors mount to the wall in a similar fashion.

    Sensors and Wiring

    • Install and connect up to 4 wired sensors to the console's wired sensor inputs.
    • Install up to 4 wireless sensors and pair them to the console — verify wireless signal strength during setup (see Troubleshooting below).
    • Each wired or wireless sensor is assigned to a dedicated relay output (Relays 1–8, plus AUX).

    Programming

    • Access the MAIN MENU via the front panel soft keys (F1/F2/F3) and unlock the console with the password (default 0800) before making changes.
    • Configure system parameter settings, then add wireless sensors (with signal-strength verification) or wired sensors (including 4-20mA sensor setup).
    • Configure the relay behavior for each sensor/zone.

    Operation

    The EA800 uses a menu-based interface with three primary screens:

    • MONITORING (home) screen — shown when there are no active alarms; lists all programmed sensors and their current readings.
    • Pending alarm display — a sensor reading exceeding its programmed limit is shown in inverse (light-on-black) text while the programmed delay period has not yet elapsed.
    • ACTIVE ALARMS screen — shown when one or more sensors are in an active alarm or warning state; multiple simultaneous alarms are all listed.

    Other operation functions include viewing sensor settings, active alarms, the alarm log, event log, sensor log, firmware information, and RF signal information for wireless sensors.

    Maintenance

    • Lock/unlock the console to prevent unauthorized programming changes.
    • Pause monitoring (and cancel pause) during service work to avoid nuisance alarms.
    • Replace, edit, or delete sensors as needed.
    • Change date/time format and settings, sensor data collection frequency, buzzer setting, and password.
    • Clear the alarm log or sensor log.
    • Update firmware, and save/load configuration settings (useful for replicating settings across multiple units).
    • Export stored alarm, event, and sensor logs to CSV files (readable in Excel or any spreadsheet program) via the console's USB port.

    Troubleshooting

    Symptom Cause Corrective Action
    Temperature reading indicates maximum when actual temp is lower Sensor or cable shorted, or sensor failed Check for shorted connections; replace damaged cable; contact Winland support if sensor has failed
    Temperature reading indicates minimum when actual temp is higher Sensor not connected, cable open, or sensor failed Verify connection to correct header pins; replace damaged cable; contact support if needed
    Temperature display doesn't match actual temperature Incorrect sensor type programmed Verify the sensor programming matches the sensor's actual operating range
    Display flashes repeatedly between the Winland logo screen and a blank screen Console repeatedly reboots / fails to complete boot Cycle power and wait before reapplying; remove any attached USB drive; contact support if it recurs
    Display flashes on the ACTIVE ALARMS screen A sensor exceeded its limit, or a wireless sensor lost communication Verify environmental conditions at the sensor; check RF signal strength for wireless sensors

    To verify wireless signal strength: unlock the console, navigate to the sensor's PERFORMANCE screen, and confirm at least 2 signal-strength bars are shown (more bars reduce alarm latency and increase battery life). If fewer than 2 bars, relocate the sensor closer to the console or reduce obstructions.

    Specifications

    Item Specification
    Dimensions Approx. 9.375" H x 8.125" W x 2.25" D (230 mm x 199 mm x 55 mm)
    Weight Console: 0.6 lb (0.27 kg); Wireless sensors: 0.26 lb (0.11 kg) with batteries
    Mounting Console mounts to standard 3-gang electrical enclosure or drywall; wireless sensors mount to drywall/similar surfaces
    Case Material ABS, UL94V-0 rated
    EA800 Power 11 to 26VDC @ 500mA, regulated & filtered; AC adapter (not included) or alarm panel
    Aux Power Out Equivalent to DC input voltage; max output current 0.5A
    Real-Time Clock Battery CR2032 (3V Cell)
    Wireless Sensor Power 12VDC @ 100mA (2.1mm barrel, center positive) or 2x AA alkaline batteries
    Low/High Limit Range – Temperature –112°F to 302°F (–80°C to 150°C)
    Low/High Limit Range – Humidity 5% to 95% RH
    Sensors Up to 4 wired + up to 4 wireless
    Cable to Wireless Multi-Function Sensor 100 ft. (30 m) maximum
    Wired Sensor Cabling Temp: 2-wire; Humidity: 3-wire; Water: 2-wire — max 1,000 ft. (304 m), 22 AWG minimum
    Relay Outputs 9 Form C, N.C./COM/N.O. (8 primary, 1 auxiliary); max 30VDC @ 1A resistive, not for AC power
    Display 128x64 graphic LCD with blue backlight
    Ethernet 10/100BASE-TX/FX, IEEE 802-3u (EA800-ip variant only)
    Operating Environment 32°F to 122°F (0°C to 50°C), 5–95% RH non-condensing, indoor non-corrosive use only. Not for installation inside coolers/freezers.
    Conformity FCC Part 15 Subpart C Class B; ICES-003 Issue 3; NRTL CUE certification
    Warranty One (1) Year Limited Warranty

    Accessories

    • BZ-1 Audible Alarm Module — buzzer for the auxiliary relay output
    • 12VDCT Power Supply — regulated 110VAC-to-12VDC @ 500mA transformer

    Manufacturer / Support

    Winland Electronics, Inc. — one-year limited warranty on materials and factory workmanship. Contact Winland Technical Support at 1-800-635-4269, Monday–Friday 8am–5pm Central. Manual and firmware resources available at www.ea800.net.