September 08, 2026 5 min read
Installation and owner's manual for the Winland EnviroAlert EA200 and EA400 environmental alarm systems.
Installation and owner's manual for the Winland EnviroAlert EA200 and EA400 environmental alarm systems, which monitor temperature, humidity, and water presence and trigger alarm relay outputs when programmed limits are exceeded.
The EnviroAlert EA200 and EA400 provide alarm signals when monitored conditions exceed user-programmable HIGH LIMIT or LOW LIMIT set points. Alarm signals are provided via relay outputs that can operate with alarm panels, process controls, security systems, or other automated equipment. Setup is done using front panel keys and an icon-based LCD display.
The EA200 and EA400 can monitor multiple critical environments using multiple sensor inputs, with each sensor input/alarm channel designated as a "Zone." The two models differ primarily in the number of zones supported:
Each zone has its own Form C relay output that activates when a monitored condition exceeds the programmed range. An AUX (Auxiliary) output relay activates whenever any zone is in alarm, useful for a single output to an alarm panel or optional audible alarm.
Using appropriate accessory sensors (sold separately), the EA200/EA400 can monitor: temperature from –50°C to 150°C (–58°F to 299°F), humidity from 5% to 95% RH, and presence of water. Units mount directly to a 2-gang electrical enclosure or to walls.
Power source must furnish REGULATED 11 to 14VDC (EA200-12 / EA400-12) or 23 to 26VDC (EA200-24 / EA400-24), via a regulated AC/DC adapter or a regulated DC power supply from an alarm panel. All terminals must be connected to a Class 2 Power Limited Circuit per NFPA 70, Article 725.
The unit uses a removable rear mounting plate. Remove the plate from the main chassis (disengage the bottom retainer tabs, then the upper hinges), then mount it either to a 2-gang electrical enclosure (4 machine screws) or directly to a drywall surface (mark hole locations, install drywall anchors). Prepare a wiring access hole at the mounting location — all wiring must pass through the opening in the center of the mounting plate.
All connections use Terminal Block Adapters (supplied with the unit and sensors). Strip wire ends, insert into the adapter, secure with set screws, then press the adapter onto the circuit board header pins.
| Connector | Function |
|---|---|
| PWR IN | Main power connection. Observe (+)/(−) polarity — reversed polarity can damage the unit. |
| PWR OUT | Powers approved accessories (e.g. HA-III Humid Alert, PN 1128). Do not connect unsuitable loads. |
| SENSOR IN 1–4 | External sensor inputs. EA200 only uses SENSOR IN 1 (Zone 2); EA400 uses all four (Zones 1–4). Only connect sensors specified in the manual. |
| AUX OUT | Form C relay that activates on any alarm; not configurable for energized/de-energized mode. |
| OUTPUT 1–4 | Per-zone Form C alarm relay outputs (EA200 uses OUTPUT 1–2; EA400 uses OUTPUT 1–4). |
Warning: Relay outputs are for low-voltage, low-current alarm connections only — not for switching AC-mains powered loads. Connecting AC-mains circuits may cause electric shock or fire hazard.
Caution: Do not connect or disconnect power, sensor, or alarm wiring with power applied.
| Key | Function |
|---|---|
| ALARM SILENCE | Interrupts the AUX output relay for 10 minutes on alarm; with ENTER, toggles Locked/Unlocked mode. |
| TIME/DATE | Accesses Time/Date set mode (when unlocked). |
| ZONE | Accesses zone programming (unlocked) or selects the zone displayed (normal operation). |
| OFFSET | Allows offset entry for the displayed zone. |
| INCREASE / DECREASE | Scrolls selections/values; toggles between zones. |
| ENTER | Saves a selection/value and advances to the next programming item. |
| ALARM HISTORY | Displays up to 8 stored alarm events (time, date, zone, limit exceeded). Hold 5 seconds to clear history. |
During normal operation the display cycles through zone readings. When an alarm condition exists, the alarm icon flashes (steady if within the delay period, flashing once the delay elapses). Use the ALARM HISTORY key to review up to 8 stored alarm events with timestamps.
| Error Display | Cause | Corrective Action |
|---|---|---|
| Flashing zone digit + "-50°C"/"-58°F" | Open connection at SENSOR IN, loose wire in terminal adapter, or defective sensor | Check connections and splices; verify adapter is seated; replace sensor if needed |
| Flashing zone digit + "150°C"/"299°F" | Shorted SENSOR IN connection or defective sensor | Check connections/splices; try another sensor and replace if needed |
| Obviously incorrect temperature reading | Wrong sensor type programmed for the zone | Match zone programming (RED/BLUE) to the sensor type actually installed |
| ERR displayed | Internal calibration error | Contact Winland Technical Service at 1-800-635-4269 |
| Item | EA200 | EA400 |
|---|---|---|
| Dimensions | Approx. 122 mm x 152 mm x 30.5 mm (4.8" H x 6.0" W x 1.2" D) | |
| Weight | 0.25 kg (0.55 lb.) | 0.27 kg (0.6 lb.) |
| Case Material | ABS, UL94V-0 rated | |
| Input Voltage | 11–14VDC (–12 models) or 23–26VDC (–24 models), regulated | |
| Adjust Range – Temperature | –50°C to 150°C (–58°F to 299°F) | |
| Adjust Range – Humidity | 5% to 95% RH | |
| Zones | 1 built-in temp zone + 1 external sensor connector (Zone 2) | 4 external sensor connectors (Zones 1–4) |
| Sensor Wiring | Temperature: 2-wire, 18-22 AWG; Humidity: 3-wire, 18-22 AWG; max 304 m (1,000 ft.) cable length | |
Winland Electronics — www.winland.com. Phone: 1-800-635-4269.