  • SECO-LARM ST-2406-3AEQ — Power Supply/Charger with Enclosure Manual

    September 08, 2026 4 min read

    Installation and reference manual for the SECO-LARM ST-2406-3AEQ ENFORCER Power Supply/Charger with Enclosure.

    Full text manual (for reference)

    Installation and reference manual for the SECO-LARM ST-2406-3AEQ ENFORCER Power Supply/Charger with Enclosure — a programmable 6/12/24VDC power supply and battery charger designed for alarm and access control system installations, with backup battery support and a heavy-duty steel enclosure.

    Overview

    The ST-2406-3AEQ ensures alarm and access control systems have reliable power. It's protected by fused battery outputs, input polarity protection diodes, and backup battery reverse-polarity protection. The enclosure has room for up to two backup batteries (leads included for one optional backup battery — up to two 4Ah batteries or one 7Ah battery fit inside).

    Features

    • Automatic recharging of backup batteries
    • Automatic switchover to backup battery if main power is lost or cut
    • Built-in battery short-circuit protection
    • Low-battery cutoff
    • LEDs indicate power status
    • Programmable DC voltage output (6V, 12V, or 24V via DIP switch)
    • Regulated and filtered output voltage
    • Fused output for a regulated charge
    • Heavy-duty steel case to protect power connections
    • Includes battery leads for easy installation
    • High efficiency at full load; heat sink free design

    Parts List

    • 1x Power supply/charger unit
    • 1x Wire relief clamp
    • 1x Small grommet
    • 3x Wire leads for backup battery
    • 2x Screw-on wire nuts
    • 1x Flange nut for wire relief clamp
    • 1x Large grommet
    • 1x Manual

    Specifications

    Spec Value
    DC voltage options 6V, 12V, 24V (DIP switch selectable)
    Operating voltage 12~24 VAC/VDC for 6VDC output, 18~24 VAC/VDC for 12VDC output, 24~28 VAC or 26~28 VDC for 24VDC output
    Status LEDs AC Input: Green; DC Output: Red/Blue (Blue = 24V)
    Current (continuous) 2.5A
    Current (peak) 3.0A
    Current output (max. charge) 6V=100mA, 12V=220mA, 24V=450mA
    Master fuse 5A
    Low battery cutoff Activates when battery voltage is <20% of set output
    Operating temperature -4° to 149°F (-20° to 65°C)
    Board dimensions 2 7/8" x 2 7/8" x 1 3/8" (73 x 73 x 35 mm)
    Enclosure dimensions 10" x 7 3/4" x 3 1/2" (254 x 196 x 89 mm)

    Overview / Layout

    The enclosure (cover removed) exposes: AC power input hole, wire relief clamp mounting screw, mounting holes, output voltage trimpot, voltage selector DIP switch, DC Output LED (red/blue), master fuse, AC Input LED (green), and backup battery outputs. Terminal blocks are labeled AC – DC + – BAT +. Knockouts for cable entry are located on the top, bottom, both sides, and back; ventilation holes are on both sides. A Class-II transformer connects to the VAC input terminals, and the alarm/access control panel connects to the VDC output terminals. Note: other mounting holes are provided for transformer mounting, and the bottom side includes two security lock holes.

    Installation

    1. Mount the power supply/charger enclosure in a location that will be easily accessible for future servicing.
    2. Set the desired DC output voltage (6, 12, or 24VDC) using the DIP switch settings below. Important: disconnect power before changing DIP switch settings. Default output is 12VDC.
    3. Connect a Class-II transformer with appropriate specifications (see transformer table below).
    4. Connect a sealed lead-acid or gel-type backup battery if desired.
    5. Connect the wires to their respective terminals. Use the supplied grommets to protect wires entering the enclosure, and secure the AC power wire with the wire relief clamp and flange nut.

    DIP Switch Voltage Settings (Table 1)

    Voltage SW1 SW2
    6V ON ON
    12V ON OFF
    24V OFF OFF

    Recommended Transformers (Table 2)

    Output Recommended Transformer
    6VDC ST-UV16-W50Q (16VAC/50VA)
    12VDC ST-UVDA-W100Q (24~28VAC/100VA)
    24VDC ST-UVDA-W100Q (24~28VAC/100VA)

    Installation Notes

    1. Before connecting any external devices, temporarily power up the unit and measure the DC output voltage at the device connection point to avoid damage to devices. If the voltage drop is large, adjust using the output voltage trimpot, then disconnect power before connecting external devices.
    2. See the LED status indicator table below.
    3. The unit ships with a 5A fuse — use only correct-rated fuses to prevent short-circuits and damage to the power supply or the connected panel.
    4. The automatic low-battery cutoff will cut power when battery voltage drops below 20% of the set output voltage.

    LED Status Indicators (Table 3)

    Green LED Red/Blue LED Status
    ON ON* Normal
    OFF ON* No VAC input
    ON OFF No VDC output
    OFF OFF No VAC input and no VDC output

    * Red = 6/12VDC, Blue = 24VDC

    Warnings

    • Installation and servicing must be performed by qualified service personnel.
    • The power supply must be installed in accordance with all national and local electrical codes.
    • Do not use a higher AC input than recommended (rated max. 28VAC).
    • Disconnect the power supply before changing DIP switch settings or performing any type of service. There are no user serviceable parts inside.
    • Do not touch any exposed metal, electrical, or electronic parts — they may become very hot under load.
    • Keep power-limited wiring separate from non power-limited wiring (115VAC input, battery wires) — provide at least 1/4" (7mm) spacing.
    • Connect only to a rechargeable backup battery. Using a non-rechargeable battery could damage the power supply/charger or the alarm/access control panel.

    Troubleshooting

    Problem Check
    No DC output Check whether AC input voltage or backup battery voltage is normal; check whether the output voltage setting is correct
    Low DC voltage output Check whether AC input wattage is correct; if battery is supplying power, check whether battery voltage is normal; check whether the power supply board is overloaded
    No backup battery power Check whether battery voltage is normal or already discharged; check whether the master fuse has burned out

    Related Products

    SECO-LARM also offers 12VDC high-amp switching CCTV power supplies, relay boards, low battery cutoff boards (ST-BD01Q), additional power supply/charger boards (e.g. ST-2406-5AQ), 12VDC plug-in AC adapters, power converters, plug-and-play backup batteries, and open-frame transformers.

    Warranty

    Warranted against defects in material and workmanship for 1 year from date of sale to the original customer, when used in normal service. SECO-LARM's obligation is limited to repair or replacement of defective parts, transportation prepaid to SECO-LARM. Void if damage is caused by acts of God, misuse/abuse, neglect, unauthorized repair or alteration, improper usage, or faulty installation. No liability for special, collateral, incidental, or consequential damages.

    SECO-LARM U.S.A., Inc. — 16842 Millikan Avenue, Irvine, CA 92606. Phone: (949) 261-2999 or (800) 662-0800. Email: sales@seco-larm.com.