  • Interlogix SafeAir 250-CO — Carbon Monoxide Detector Data Sheet

    September 08, 2026 3 min read

    Data sheet for the Interlogix SafeAir 250-CO, a 12/24VDC hardwired carbon monoxide detector with SafeTest functional testing.

    Full text manual (for reference)

    Data sheet for the Interlogix SafeAir™ 250-CO — a 12/24VDC hardwired carbon monoxide detector with SafeTest™ functional testing, designed to interface with any UL 985/864 listed intrusion or fire alarm system.

    Overview

    The SafeAir 250-CO uses an electro-chemical CO sensor with an on-board microprocessor that tracks CO levels over time, self-adjusts for environmental changes, and compensates for sensitivity drift over its service life. It connects to a Class 2 output from a control panel or auxiliary power supply and reports alarm and trouble conditions via relay to the panel and (if monitored) the central station.

    Standard Features

    • SafeTest™ enables a full functional test using real CO test spray (meets NFPA 720 2009/2012 functional test requirement)
    • Electro-chemical sensing technology, fully listed to UL 2075
    • Transmits sensor end-of-life status to the control panel and central station if monitored
    • Built-in trouble/power supervision relay; six-year sensor life
    • Self-diagnostics keep the device operating optimally throughout its service life
    • 12 or 24VDC operation; 150mA relay contact, configurable normally open or normally closed
    • Large SEMS terminals for 14–22 AWG wiring
    • One-touch TEST/HUSH button; integrated 85 dBA temporal-4 sounder
    • On-board LED for local alarm and trouble indication
    • Optional adapter plate (P/N 250-COPLT-5PKG) for simple replacement of the ESL 240-COe CO detector

    Recommended Installation Locations

    Install per NFPA 720. Wall-mounted detectors: at least 5 ft. (1.5 m) up from the floor. Ceiling-mounted: at least 1 ft. (0.3 m) from any wall.

    • Within 10 ft. (3 m) of all sleeping areas, including hotel/dorm rooms
    • Environments between 32–104°F (0–40°C), 0–90% relative humidity, noncondensing
    • Residential: in every bedroom, within 10 ft. of sleeping areas, and on each level (minimum one detector outside sleeping areas)
    • Commercial: on every habitable level per engineering evaluation; any area required by local codes/AHJ; firm, permanent surfaces

    Do NOT install: within 10 ft. (3 m) of a fuel-burning appliance; near air conditioners, heating registers, or ventilation sources; where furniture/draperies obstruct airflow; or in a recessed area.

    Operation

    • SafeTest functional test: Press and hold TEST/HUSH for 5–10 seconds to enter SafeTest mode, then direct UL-classified CO test spray at the sensor port to verify alarm activation (temporal-4 sounder + red LED). Press and hold again to exit.
    • Sounder: 85 dB temporal-4 pattern — four beeps, five-second rest, repeat.
    • TEST/HUSH button: Tests the alarm or silences an active alarm for five minutes (does not silence above 350 ppm CO).
    • End-of-life indicator: Flashing green LED plus intermittent sounder chirps; silence with TEST/HUSH. Reports trouble to the panel as the sensor approaches end-of-life.
    • Common trouble relay: Opens on lost power, sensor cell trouble, or cell end-of-life.

    Installation & Wiring

    Four-wire device requiring a Class 2 output from a control panel or resettable auxiliary power supply listed to UL 985 or 864. All wiring must conform to NFPA 70 (National Electric Code), UL 2075, NFPA 720, and local codes, using 14–22 AWG wire. Supports single-device/single-zone, multiple-devices/single-zone, and multiple-devices/separate alarm-trouble-zone wiring configurations (see full wiring diagrams in the downloadable PDF).

    Warning: Connect the CO detector only to a zone dedicated exclusively to CO detection, monitored 24 hours a day. Do not connect to an initiating circuit with fire or security devices. Failure to properly install, test, and maintain a CO detector may result in loss of life.

    Specifications

    Spec Value
    Input voltage 12 or 24 VDC, supplied by control panel or resettable auxiliary power supply
    Current draw Normal 20 mA; Alarm 40 mA (75 mA in test)
    Alarm relay 150 mA at 33 VDC, Form C, Zone rated
    Common trouble relay 150 mA at 33 VDC, normally open held closed with power applied
    CO alarm response time 70 PPM: 60–240 min · 150 PPM: 10–50 min · 400 PPM: 4–15 min
    Sounder 85 dB, temporal-4 pattern
    Compatible control panel Listed to UL 985 or 864
    Electrical box North American 2½ in. (64 mm) deep, 1-gang
    Wire size 14 to 22 AWG (0.25–2.0 mm²)
    Dimensions (detector) 3.1 x 4.6 x 1.3 in. (7.8 x 11.7 x 3.2 cm), 4.7 oz. (133 g)
    Dimensions (adapter plate) 4.5 x 6.5 x 0.2 in. (11.4 x 16.5 x 0.5 cm), 1.6 oz (46 g)
    Color White
    Operating environment 32–104°F (0–40°C), 0–90% RH noncondensing
    UL rating Listed to ANSI/UL 2075

    Ordering Information

    • 250-CO: SafeAir Carbon Monoxide Detector, alarm & trouble relays, sounder, end-of-life signal, 12/24VDC
    • 250-COPLT-5PKG: Adapter plate for replacing the 240-COe CO detector with a 250-CO
    • CO Gas Test Spray: Functional CO gas test spray (Solo C-6, available through security distribution from SDI, www.sdifire.com)