Full installation and programming manual for the GE Security Quik Bridge Loop Receiver, which adds wireless sensors to hardwire control panels.
Full installation and programming manual for the GE Security Quik Bridge Loop Receiver — lets you add up to 16 Learn Mode wireless sensors (two per zone), 45 Keychain Touchpads, and panic button transmitters (61 wireless transmitters total) to any standard hardwire control panel.
The Quik Bridge Loop Receiver monitors alarm, battery, tamper, and supervisory status of transmitters learned into its eight zones. It is compatible with control panels designed with hardwire loops where the loop negative is ground (common-loop ground).
Compatible with all current Learn Mode™ sensors (319.5 MHz), panic button transmitters, and 2/4-button Keychain Touchpads. Compatible panels (one or more versions supporting common-loop ground) include ADT SafeWatch, Ademco 4110XM/Vista 10/Via 30P, C&K System 236, DSC PC1550/Power 832 PC5010, First Alert FA 1330C, Moose Z1100e, Napco Magnum Alert 1008e/M, and Radionics D9112B. If your panel isn't listed, test for compatibility (see below).
Caution: Not directly compatible with powered loops (2-wire smoke/glass-break loops) — connecting directly can permanently damage the receiver; a relay must be installed for powered loops.
A single DIP switch controls the mode: switch up = Program Mode, switch down = Run Mode. Main components include antenna terminal blocks, Select (SEL) and Advance (ADV) switches, tamper switch, DIP switch, LEDs, and the receiver terminal strip (numbered 1-8 zone outputs, B, S trouble outputs, T test output, GND, GND, +12V).
Eight zone outputs (1-8). When a learned transmitter activates, the corresponding output switches to alarm state for at least 3 seconds until the transmitter restores. Zone 7 doubles as RF Jam Detect (trips after a 30-second constant signal) if no transmitter is learned into it — learning a transmitter into zone 7 disables jam detection. Zone 8 doubles as Receiver Cover/Antenna Tamper if no transmitter is learned into it — learning a transmitter into zone 8 disables tamper detection.
| Power LED | Indicates |
|---|---|
| On steady | Receiver has power, functioning normally |
| Off (all other LEDs off) | Receiver not properly wired or power failure |
| Off (yellow LEDs blinking) | Receiver failed power-up self-test |
| Blinks off momentarily | Received an RF signal (learned or not) |
In Run Mode, zone LEDs indicate alarm/tamper (on = open, off = closed/unused); the yellow Low Battery LED and Supervisory LED flash in sync with the affected zone's LED to help diagnose which zone/transmitter has the issue.
Installation guidelines: leave 10" above the receiver for the antenna; avoid moisture-prone areas; avoid excessive metal or electrical wiring (furnace/utility rooms). If mounting on metal is unavoidable, ensure the antenna extends above the metallic surface.
To delete a Keychain Touchpad, repeat for each button learned into a zone — it's fully deleted only when all its learned buttons are removed.
For both trouble outputs: press the tamper switch once, then ADV nine times (until all zone LEDs are off) to reach trouble outputs, then SEL to toggle (low battery LED on = N/C, flashing = N/O).
All 8 zones default to supervised. Enter Program Mode, press the tamper switch twice to access supervision config, then ADV/SEL to toggle each zone (LED on = supervised, off = unsupervised). Note: Keychain Touchpads are never supervised; panic buttons in zone 1 are not supervised.
Zone outputs 3-6 can be momentary or maintained (toggle). Enter Program Mode, press the tamper switch once, ADV to the desired zone (3-6), then SEL to toggle (LED off = maintained, on = momentary).
Four wiring configurations are supported depending on the panel loop type: supervised N/O loop (with EOL resistor), N/C loop (with EOL resistor), non-supervised loop, and a relay-based configuration for powered loops. Multiple normally-open loop receiver zone outputs can be connected in parallel to panel zone inputs.
Test two ways: (1) count LED flashes when transmitters are tripped, or (2) count beeps from an optional piezo beeper connected to the T (test) and GND terminals. Make sure the DIP switch is down (Run Mode), then trip all sensors and observe/listen.
| Transmitter | Should Cause |
|---|---|
| Sensors | 7-8 beeps and LED flashes |
| Keychain touchpad — 1-button press | 2 beeps and LED flashes |
| Keychain touchpad — 2-button press | 8 beeps and LED flashes |
| Compatibility | Control panels with common-loop ground hardwire loops |
| Power requirements | 10.0 – 14.0 VDC |
| Current draw | 60 mA maximum |
| Open collector outputs (1-8, B, S) | Max applied voltage 16 VDC; max sink current 50mA (typical), 15mA (minimum) |
| Operating temperature | 40° to 120°F |
| Dimensions | 4.125" x 5.25" x 1" (L x W x H), excluding antenna |
Manufacturer: UTC Fire & Security Americas Corporation, Inc., 1275 Red Fox Rd., Arden Hills, MN 55112-6943. Complies with FCC Part 15 Class B. This device may not cause harmful interference and must accept any interference received, including interference that may cause undesired operation. Contact: www.utcfireandsecurity.com or www.interlogix.com.