September 08, 2026 4 min read
Installation and programming instructions for the GE/Interlogix NX-208E Two-Wire Smoke Loop Expander for NetworX NX-6/NX-8 series control panels.
Installation and startup instructions for the GE Security/Interlogix NX-208E Two-Wire Smoke Loop Expander, a microprocessor-controlled zone expander for NetworX NX-6, NX-8, NX-8-CF, NX-8E, and NX-8E-CF control panels.
The NX-208E is a microprocessor-controlled 2-wire smoke expander for the NetworX NX-6, NX-8, NX-8-CF, NX-8E, and NX-8E-CF control panels. One NX-208E module can be added to the NX control panel with a maximum zone count of 8 zones. Each expander has an optional tamper input, making it ideal for use in a remote location.
Important: Do not add normally open contact devices to an NX-208E loop (i.e. sounders, heat detectors, pull stations, water flow devices, etc.)
Inside the can, several 2-holed insertion points allow for either vertical or horizontal placement of the modules. Each insertion point has two sizes of holes — a larger hole and a smaller hole.
Static caution: Be free of static electricity before handling circuit boards. Wear a grounding strap or touch a bare metal surface to discharge static electricity.
| Terminal | Function |
|---|---|
| TAMPER / COM | Connect normally closed tamper switch between this pin and COM. |
| DATA | Connect to the DATA terminal of the control panel. |
| COM | Connect to the COM terminal of the control panel. |
| AUX+ | Connect to the AUX+ terminal of the control panel. |
| DCIN | Optionally connect to an auxiliary 12V or 24V power supply (e.g. NX-320E). Be sure to connect GND of the power supply to the NX-208E. |
| ZONE8- / ZONE8+ | Connect to negative/positive side of the smoke detector. Open (trouble) or short (alarm) sounds the keypad by default (programmable). |
| ZONE7- through ZONE1+ | Wired the same way as ZONE8-/ZONE8+. |
NX-208E DCIN rating: 31mA at 12 VDC / 62mA at 24 VDC; Maximum 3.84 Amps with 8 detectors per loop. NX-208E AUX+ rating: 31mA in at 12VDC in Normal Standby or Alarm condition.
NetworX control panels automatically find and store the presence of all keypads, zone expanders, wireless receivers, and other modules connected to the data terminal, allowing them to be supervised. To enroll, enter the Program Mode of the control panel; when Program Mode is exited, the panel automatically enrolls the devices. Enrollment takes about 12 seconds, during which the "Service" LED illuminates. If a module is not detected after enrollment, the "Service" LED will illuminate.
Module Address: This 2-wire smoke module has a fixed address of 95.
Used to enable/disable zones 1–8 (1=Zone1 ... 8=Zone8). Factory default: all zones disabled.
Selects the bank used by zones 1–192 during communication (a zone may reside in any of 24 banks). Entering [1] through [23] remaps zones 1–8 in Location 0 to the corresponding range (e.g. entering [9] causes zone 1 to become zone 73, zone 8 becomes 80). Factory default: 1 (Zones 9–16).
Factory default: all flags disabled.
| Type | Compatible Devices |
|---|---|
| S09A | 429AT, 521B/BXT (SW1 ON), 521NB/NBXT |
| S10A | 521NB, 521NBXT, 521NCSXT, 429C, 429CT, 521B/BXT (SW1 OFF), 711U/UT, 721U/UT |
| S11A | 429CRT, 429CST, 521CRXT, 521NCRXT, 521NCSRXT, 731U |
| Spec | Value |
|---|---|
| Operating Power | 12VDC, supplied from NetworX NX-6/8/8-CF/8E/8E-CF or NX-320E (must be UL listed for Commercial Fire or Burglary) |
| Auxiliary Power | Supplied from NetworX models; current limited to 100mA |
| Current Draw | 30mA |
| DCIN Current Draw | 31mA max @ 12VDC / 62mA max @ 24VDC |
| AUX+ Rating | 13mA @ 12VDC standby / 53mA @ 12VDC alarm |
| Loop Resistance | 12V loop: 20 Ohms max / 24V loop: 50 Ohms max |
| Loop Response | 180mS |
| Operating Temperature | 32 to 120°F |
| Dimensions | 9.5" W x 3.5" H x 1.0" D |
| Shipping Weight | 2 lbs. |
UL609 (Local Grade A Mercantile, Police Station Connect), UL864 (Control Units for Fire-Protective Signaling Systems), UL985 (Household Fire Warning Systems), UL1023 (Household Burglary Alarm Systems), UL1610 (Grade B & C Central Station Burglar Alarm Unit). Canada/ULC: S303, S304, S545.
| Part # | Description |
|---|---|
| NX-208E | Two Wire Smoke Loop Expander |
| EOL33 | 3.3K End-of-Line Resistor device |
| NX-216E | 16 Zone Expander Module |
| NX-320E | Smart Power Supply and Buss Extender |
| NX-507E | Seven Relay Module |