GE Security Photoelectric Smoke/Heat Detector w/Sounder, 4-Wire
GE449CST
PRICE: $64.95
|
 |
|
|
GE SECURITY SELF-DIAGNOSTIC SMOKE DETECTOR WITH SOUNDER
PHOTOELECTRIC 4-WIRE, HEAT SENSOR, SOUNDER, 12/24 VDC
The GE449 Series self-diagnostic, four-wire smoke detectors continually monitor their own sensitivity and operational status, and provide a visual trouble indication if they drift out of sensitivity range or fail internal diagnostics. This unique, patented technology meets NFPA 72 field sensitivity testing requirements without the need for external meters. Additional diagnostic information is activated by applying a magnet near the detector's integral reed switch. This initiates a self-diagnostic routine and provides visual indication of sensitivity level, or if service is required. This series is easily cleaned by simply replacing GE Security's proprietary field-replaceable optical chamber. All models are designed to reduce false alarms from dust, insects, RFI, and external light.
INCREASE YOUR SAFETY & SECURITY
Most homes have battery operated ionization smoke detectors. These detectors react quickly to flaming fires but usually take longer to detect smoldering fire – the most common type of fire that occurs in homes. GE Interlogix ESL smoke detectors utilize photoelectric smoke detection technology. Photoelectric smoke detectors continually analyze the air for smoke particles and are more sensitive to smoldering fires than ionization detectors. Installing both ionization and photoelectric smoke detectors in your home provides the best possible protection for you and your family. You can count on GE to protect your family and investment. Photoelectric alarms are essential in your applications.
Check out these additional products:
GE Security Photoelectric Smoke Detector, 4-Wire, End of Relay
GE SafeAir Carbon Monoxide Alarm

449CST Series Photoelectric Smoke Detector Datasheet (.pdf)
Standard Features:
- Intelligent, self-diagnostics
- On-site maintenance alert
- Field replaceable optical chamber
- Low-profile design
- Plug-in terminal block
- Advanced false alarm immunity
Specifications:
- Alarm @ Relay Specifications: 2.0 A @ 28.0 V
- Alarm Current Consumption [Nominal]: 40.0 mA
- Color: White
- Current Comsumption w/ Alarm [Nominal]: 40.0 mA
- Detection (Operating) Range: 3.1 to 1%/ ft max; 3.1 to.5%/ft max
- Detector Head Depth [Nominal]: 1.85 in
- Detector Head Diameter [Nominal]: 6.1 in
- Field Wiring Size [Minimum]: 14.0 AWG
- Field Wiring Size [Maximum]: 24.0 AWG
- Heat Detection Specifications - Fixed [Nominal]: 135.0 °F
- Heat Detection Specifications - Rate of Rise: >105°F and Rate of Rise 15°F/min
- Height [Nominal]: 1.85 in
- Maximum Ripple [Maximum]: 10.0 %
- Operating Humidity [Minimum]: 0.0 % RH
- Operating Humidity [Maximum]: 95.0 % RH
- Operating Temperature [Minimum]: 32.0 °F
- Operating Temperature [Maximum]: 120.0 °F
- Operating Voltage [Minimum]: 8.5 V
- Operating Voltage [Maximum]: 33.0 V
- Packaging Basis [Nominal]: 10.0 per carton
- Polarity Reverse Current [Nominal]: 10.0 mA
- Regulatory Approval: UL 268, ULC, FM, CSFM, MEA
- Relay @ Contact Rating: 500.0 mA @ 36.0 V
- Sensitivity - Photoelectric [Minimum]: 0.05 %
- Sensitivity - Photoelectric [Maximum]: 3.1 %
- Sensitivity - Photoelectric [Nominal]: 3.1 %
- Sounder Specifications [Nominal]: 8.5 db/ft
- Standby Current Consumption [Nominal]: 70.0 µA
|