GE Security Photoelectric Smoke/Heat Detector, 4-Wire
GE449CT
An integral combination rate-of-rise and fixed 135°F (57°C), 50-foot rated, heat sensor is available with all “T“ model detectors.
Price: $54.95
|
|
Product Description
|
GE SECURITY SMOKE DETECTOR, PHOTOELECTRIC, 4-WIRE, HEAT SENSOR
CONTAINS RATE-OF-RISE HEAT SENSOR
The 449 series self-diagnostic, 4-wire smoke detectors continually monitor their own sensitivity and operational status, and provide a visual trouble indication if they drift out of sensitivity range or fail internal diagnostics.
The 449 series is easily cleaned by replacing the proprietary fieldreplaceable optical chamber. All models are designed to reduce false alarms from dust, insects, RFI and external light.
An integral combination rate-of-rise and fixed 135°F (57°C), 50-foot rated, heat sensor is available with all “T“ model detectors. GE SECURITY SMOKE DETECTORS WITH CleanMe The GE FX7 Series conventional self-diagnostic, smoke detectors, with CleanMe continually monitor their own sensitivity and operational status, and provide a trouble condition at the FireworX conventional control panel and FX detector if they drift out of sensitivity range or fail internal diagnostics. This meets NPFA 72 field sensitivity requirements without the need for external meters. Additional diagnostic information is activated by applying a magnet near the detector's integral reed switch. This initiates a self-diagnostic routine and provides visual indication of sensitivity level, or if service is required.
If the 400 Series ever does require cleaning simply replace GE's patented field-replaceable optical chamber. All models are designed to reduce false alarms from dust, insects, RFI and external light.
An integral combination rate-of-rise and fixed 135°F (57°C), 50-foot rated, heat sensor is available with all “T“ model detectors. An integrated silicon heat sensor and a dedicated microprocessor are used to detect heat and perform the rate of rise calculations, for earlier heat detection. The 400 Series models allow latching of the alarm for either smoke or heat. |
Specifications
|
|
GE Security 449CT Install Guide (.pdf)
GE Security 449CT Tech Bulletin (.pdf)
Standard Features: - Intelligent self-diagnostics
- Field-replaceable optical chamber
- Low-profile design
- Plug-in terminal block
- Advanced false alarm immunity
- Meets NFPA 72 field sensitivity testing requirements without the need for external meters
- On-site maintenance alert
| Alarm @ Relay Specifications | 2.0 A @ 28.0 V | Alarm Current Consumption[Nominal] | 15.0 mA | Color | White | Current Comsumption w/ Alarm[Nominal] | 15.0 mA | Detection (Operating) Range | 3.1 to 1%/ ft max; 3.1 to.5%/ft max | Detector Head Depth[Nominal] | 1.85 in | Detector Head Diameter[Nominal] | 6.1 in | Field Wiring Size[Minimum] | 14.0 AWG | Field Wiring Size[Maximum] | 24.0 AWG | Heat Detection Specifications - Fixed[Nominal] | 135.0 °F | Heat Detection Specifications - Rate of Rise | >105°F and Rate of Rise 15°F/min | Height[Nominal] | 1.85 in | Maximum Ripple[Maximum] | 10.0 % | Operating Humidity[Minimum] | 0.0 % RH | Operating Humidity[Maximum] | 95.0 % RH | Operating Temperature[Minimum] | 32.0 °F | Operating Temperature[Maximum] | 120.0 °F | Operating Voltage[Minimum] | 8.5 V | Operating Voltage[Maximum] | 33.0 V | Packaging Basis[Nominal] | 10.0 per carton | Polarity Reverse Current[Nominal] | 10.0 mA | Regulatory Approval | UL 268 ULC FM CSFM MEA | | Relay @ Contact Rating | 500.0 mA @ 36.0 V | Sensitivity - Photoelectric[Minimum] | 0.05 % | Sensitivity - Photoelectric[Maximum] | 3.1 % | Sensitivity - Photoelectric[Nominal] | 3.1 % | Sounder Specifications[Nominal] | 8.5 db/ft | Standby Current Consumption[Nominal] | 70.0 µA |
|
|
|
|
|
|
|
|